| Plan Review Notes For Permit 21111211 |
| Permit Number |
21111211 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-07 10:59:13 | SHEET P3.1; THE CONDENSATE DRAIN PIPE MUST MEET THE | | | MINIMUM SIZE. | | | | | | 307.2.2 DRAIN PIPE MATERIALS AND SIZES. COMPONENTS OF | | | THE CONDENSATE DISPOSAL SYSTEM SHALL BE CAST IRON, | | | GALVANIZED STEEL, BRASS, COPPER AND COPPER ALLOY, | | | CROSS-LINKED POLYETHYLENE, POLYETHYLENE, ABS, CPVC, | | | PVC, OR POLYPROPYLENE PIPE OR TUBING. COMPONENTS SHALL | | | BE SELECTED FOR THE PRESSURE AND TEMPERATURE RATING OF | | | THE INSTALLATION. JOINTS AND CONNECTIONS SHALL BE MADE | | | IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF CHAPTER | | | 7 OF THE FLORIDA BUILDING CODE, PLUMBING RELATIVE TO | | | THE MATERIAL TYPE. CONDENSATE WASTE AND DRAIN LINE SIZE | | | SHALL BE NOT LESS THAN 3/4-INCH (19.1 MM) INTERNAL | | | DIAMETER AND SHALL NOT DECREASE IN SIZE FROM THE DRAIN | | | PAN CONNECTION TO THE PLACE OF CONDENSATE DISPOSAL. | | | WHERE THE DRAIN PIPES FROM MORE THAN ONE UNIT ARE | | | MANIFOLDED TOGETHER FOR CONDENSATE DRAINAGE, THE PIPE | | | OR TUBING SHALL BE SIZED IN ACCORDANCE WITH TABLE | | | 307.2.2. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|