| Plan Review Notes For Permit 21111193 |
| Permit Number |
21111193 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-07 17:24:21 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WOOD COLUMNS ARE SHOWN IN CONTACT WITH THE | | | GROUND AS WELL AS THE CONCRETE PAVERS. THE WESTERN | | | CEDAR WOOD THAT IS SPECIFIED IS NOT AN APPROVED | | | NATURALLY DECAY RESISTANT WOOD. FBC-R317.1.4 WOOD | | | COLUMNS SHALL BE APPROVED WOOD OF NATURAL DECAY | | | RESISTANCE OR APPROVED PRESSURE-PRESERVATIVE-TREATED | | | WOOD. | | | | | | 2) SPECIFY THE REQUIRED EMBED DEPTH OF THE COUNTER SUNK | | | WOOD SCREWS THAT SECURE THE 2 X 8S TO THE 2 X 12 BEAMS. |
|