Plan Review Notes
Plan Review Notes For Permit 21111184
Permit Number 21111184
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-15 08:04:45FLOORING REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE TYPE OF
 FLOORING AND THE LOCATION OF THE FLOORING - ALSO SHOW
 THE SQUARE FOOTAGE FOR EACH FLOORING TYPE.
  
 2) PLEASE SHOW THE ADDITIONAL JOB VALUE ON THE PLAN
 REVIEW REQUEST FORM IN THE SPACE PROVIDED.
  
 3) ACUSTICAL TEST REPORT PROVIDED FOR "MAXXIM SIM 90
 UNDERLAYMENT" SHOWS A DROP CEILING - TEST REPORT CANNOT
 INCLUDE A DROP CEILING UNLESS THE DROP CEILING
 DESCRIPTION MATCHES YOUR CEILING.
  
 4) PLEASE PROVIDE A FLAME SPREAD TEST REPORT FOR THE
 WOOD FLOORING - FBC 603.1, ALLOWABLE MATERIALS IN NON
 COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.