| 2022-02-01 12:09:05 | 1. PROPOSED PARKING CONFIGURATION NOT PERMITTED. CANNOT |
| | HAVE CARS UTILIZING THE STREET TO MANEUVER, NOT ENOUGH |
| | SPACE TO ENTER/EXIT PARKING. |
| | - BUILDING IS EXISTING THEREFORE PARKING IS NOT |
| | REQUIRED. |
| | |
| | 2. PLEASE CONFIRM COMPLIANCE WITH NWD-5 SUBDISTRICT'S |
| | TRANSPARENCY REQUIREMENTS. |
| | - MINIMUM TRANSPARENCY FOR ACTIVE USES ON GROUND FLOOR |
| | ALONG A PRIMARY PEDESTRIAN STREET (N ROSEMARY) IS 50% |
| | AND ALONG RESIDENTIAL IS 30% (8TH STREET) |
| | SEC.94-109 TRANSPARENCY MAY BE PROVIDED THROUGH THE USE |
| | OF WINDOWS AND DOOR GLAZING AS WELL AS UNOBSTRUCTED |
| | OPENINGS IN THE BUILDING FACADE. |
| | TRANSPARENCY IS REQUIRED AS A PERCENTAGE OF THE |
| | STOREFRONT FACADE AREA. |
| | |
| | 3. PLEASE PROVIDE DETAILS OF FACADE PROJECTIONS |
| | (AWNINGS) VERTICAL CLEARANCE IS 8' MIN, HORIZONTAL |
| | PROJECTION IS 3' MIN AND 8' MAX. |
| | |
| | 4. ANY NEW GROUND-MOUNTED MECHANICAL EQUIPMENT SHALL BE |
| | SCREENED FROM VIEW WITH LANDSCAPE HEDGES. ANY NEW |
| | MECHANICAL EQUIPMENT ON THE ROOF SHALL BE SCREENED FROM |
| | VIEW WITH A SCREEN EQUAL TO THE HEIGHT OF THE |
| | EQUIPMENT. |
| | |
| | 5. PLEASE PROVIDE A RECENT SURVEY OF THE PROPERTY. |
| | |
| | PLEASE SUBMIT SEPARATE PERMITS FOR LANDSCAPE, |
| | IRRIGATION, AWNINGS, SIGNAGE, ETC. AS IS NECESSARY OR |
| | APPLICABLE TO THE PROJECT. |