| 2022-02-16 16:44:24 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21111150 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING |
| | INDICATING THAT THE HOOD SYSTEM WILL REQUIRE A SEPARATE |
| | PERMIT SUBMITTAL AND PLAN REVIEW AS IT WILL NOT BE |
| | COMPLETED UNDER THIS PERMIT. |
| | |
| | 2) PLEASE SHOW THE REQUIRED OUTDOOR AIR CALCULATIONS |
| | FOR THIS KITCHEN. THE OCCUPANT LOAD FOR THIS BUILDING |
| | SHOULD BE BASED FROM THE FBC M 403.3.1.1 AND TABLE |
| | 403.1.1 WHICH WOULD BE 20 OCCUPANTS |
| | |
| | 3) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC |
| | C402.1 |
| | |
| | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 5) IF THE MECHANICAL SYSTEMS ARE TO BE USED FOR ANY OF |
| | THE MAKE UP AIR REQUIRED FOR THE HOOD SYSTEM PLEASE |
| | SHOW THIS ON THIS SUBMITTAL AND THE REQUIRED CFM?S. FBC |
| | M 508.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |