| 2022-02-22 06:48:27 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21111137 |
| | ADD: 1551 FORUM PLACE PL. # 100A |
| | CONT: HALLMARK CONSTRUCTION LLC |
| | TEL: 561-586-7664 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. FEB. 22/2022 |
| | ACTION: DENIED |
| | |
| | 1-4) COMPLIED. |
| | |
| | 5) 2ND REQUEST. ***** NOTICE ONLY ***** 4X FEE / |
| | NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT |
| | TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | UNDER THE 2020 FBC-EXISTING BUILDING CODE SECTION |
| | 805.3.1EVERY TORY UTILIZED FOR HUMAN OCCUPANCY ON WHICH |
| | THERE IS WORK AREA THAT INCLUDES EXITS OR CORRIDORS |
| | SHARED BY MRE THAN ONE TENANT WITHIN THE WORK AREA |
| | SHALL BE PROVIED WITH MINIMUM NUMBER OF EXITS BASED ON |
| | THE OCCUPANCY AND OCCUPANT LOAD IN ACCORDANE WITH THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | SHARED EXIT, CONSTRUCTION TYPE III-B, NOT SPRINKLERED, |
| | OCCUPANT LOAD OF SHARED FIRE RATED COORIDOR IS 56 |
| | (SHEET A-1). PLEASE SEE TABLE 1020.1 CORRIDOR FIRE |
| | RESISTANCE RATING, BUSINESS>30 OCC. REQUIRES A 1 HOUR |
| | FIRE RATING!!! FIRE DAMPERS REQUIRED PER 717.5.2 NOT |
| | SHOWN ON SHEET M-1. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A1 SHOWS AT THE REAR OF |
| | THE TENANT SPACE THERE IS A ONE-HOUR FIRE RATED SHARED |
| | CORRIDOR. SHEET M-1 SHOWS AIR CONDITIONING DUCTS AND |
| | RETURN DUCTS ENTERING THE ONE-HOUR FIRE RATED CORRIDOR |
| | WITH NO FIRE DAMPER. PLEASE SHOW COMPLIANCE WITH THE |
| | 2020 FBC-BUILDING CODE SECTION 717.5.2. |
| | |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |