| 2022-02-17 15:17:30 | SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21111124 |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- BASED ON AERIAL VIEW (SITE MAP) SUBMITTED AND FIGURE |
| | R301.2(7) FBC-RESIDENTIAL IT LOOKS THE SKYLIGHTS ARE |
| | GOING TO BE INSTALLED ON ROOF ZONE 2R. THE DESIGN |
| | PRESSURES ON SOLATUBE FLORIDA PRODUCT APPROVAL |
| | SUBMITTED ARE +/-70.0PSF. BASED ON CITY RECORDS THE |
| | ROOF PITCH IS 6:12 AND THE MEAN ROOF HEIGHT IS |
| | APPROXIMATELY 18'. THE DESIGN PRESSURES OF PRODUCT |
| | APPROVAL DON'T MEET THE DESIGN PRESSURES FOR ROOF ZONE |
| | 2R AS SHOWN ON TABLE R301.2(2) FBC-RESIDENTIAL. PROVIDE |
| | PRODUCT APPROVAL FOR SOLATUBE SKYLIGHT THAT MEETS THE |
| | DESIGN PRESSURES FOR ROOF ZONE 2R OR PROVIDE SITE |
| | SPECIFIC CALCULATIONS (SIGNED AND SEALED) SHOWING THAT |
| | THE SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS |
| | ROOF ZONE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | |
| | RESPONSE: |
| | ONLY THE AERIAL VIEW (SITE MAP) DRAWINGS WAS |
| | RESUBMITTED. THIS DOESN'T ADDRESS THE COMMENT. NEED TO |
| | PROVIDE PRODUCT APPROVAL WITH DESIGN PRESSURES OF -74.3 |
| | P.S.F OR HIGHER OR PROVIDE SITE SPECIFIC CALCULATIONS |
| | (SIGNED AND SEALED) SHOWING THAT THE SUBMITTED PRODUCT |
| | APPROVAL IS ADEQUATE FOR THIS ROOF ZONE. SEC. 107.2.1.2 |
| | CITY AMENDMENTS. |
| | |