| 2022-01-19 14:42:21 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21111124 |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- BASED ON AERIAL VIEW (SITE MAP) SUBMITTED AND FIGURE |
| | R301.2(7) FBC-RESIDENTIAL IT LOOKS THE SKYLIGHTS ARE |
| | GOING TO BE INSTALLED ON ROOF ZONE 2R. THE DESIGN |
| | PRESSURES ON SOLATUBE FLORIDA PRODUCT APPROVAL |
| | SUBMITTED ARE +/-70.0PSF. BASED ON CITY RECORDS THE |
| | ROOF PITCH IS 6:12 AND THE MEAN ROOF HEIGHT IS |
| | APPROXIMATELY 18'. THE DESIGN PRESSURES OF PRODUCT |
| | APPROVAL DON'T MEET THE DESIGN PRESSURES FOR ROOF ZONE |
| | 2R AS SHOWN ON TABLE R301.2(2) FBC-RESIDENTIAL. PROVIDE |
| | PRODUCT APPROVAL FOR SOLATUBE SKYLIGHT THAT MEETS THE |
| | DESIGN PRESSURES FOR ROOF ZONE 2R OR PROVIDE SITE |
| | SPECIFIC CALCULATIONS (SIGNED AND SEALED) SHOWING THAT |
| | THE SUBMITTED PRODUCT APPROVAL IS ADEQUATE FOR THIS |
| | ROOF ZONE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |