| 2022-01-04 10:05:36 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21111118 |
| | 12/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A0.0, A0.2 & A1.1: PROVIDE AN ENLARGED |
| | DRAWING OF PRIVATE RESTROOM 1662 WITH ALL APPLICABLE |
| | ACCESSIBILITY DETAILS IN ACCORDANCE WITH THE FLORIDA |
| | ACCESSIBILITY CODE- 2020. PLEASE NOTE SHEET A0.2 |
| | REFERENCES ADA HOWEVER THE PROPOSED PROJECT IS IN |
| | DESIGNED IN ACCORDANCE WITH THE FBC ACC. PLEASE PROVIDE |
| | THE FOLLOWING DETAILS. PLEASE NOTE THAT SOME |
| | COMPLIANCES LISTED MAY NOT BE REQUIRED FOR A PRIVATE |
| | OFFICE BATHROOM. PLEASE REVIEW THE CODE SECTIONS AND |
| | SHOW COMPLIANCE WHERE REQUIRED. |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- 606.2. |
| | C) TURNING SPACE DIAMETER- 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- 604.4. |
| | F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- 606.3. |
| | G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACE- 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- 604.6. |
| | J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE |
| | 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- 606.2. |
| | |
| | 2) A1.1 & A3.1: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND |
| | DIMENSIONS FOR THE BREAKROOM SINK AND APPLIANCES- SECS. |
| | 606.2 & 804.6.1 FBC P. PLEASE NOTE THAT THERE ARE TWO |
| | PLAN SHEETS LABELED A3.1- PLEASE CORRECT- SEC. 107.2.1 |
| | WPB. |
| | |
| | 3) A3.1: SHOW THE LOCATION OF THE COFFEE MAKER IN |
| | DETAIL K10, AND INDICATE THE CONTROL IS IN COMPLIANCE |
| | WITH SEC. 308 & 309 FBC ACC - REACH RANGE AND OPERABLE |
| | PARTS. |
| | |
| | 4) A3.1: SHOW THE COMBINATION REFRIGERATOR/FREEZER HAS |
| | AT LEAST 50 PERCENT OF THE FREEZER SPACE 54 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE CLEAR |
| | FLOOR OR GROUND SPACE SHALL BE POSITIONED FOR A |
| | PARALLEL APPROACH TO THE SPACE DEDICATED TO A |
| | REFRIGERATOR/FREEZER WITH THE CENTERLINE OF THE CLEAR |
| | FLOOR OR GROUND SPACE OFFSET 24 INCHES MAXIMUM FROM THE |
| | CENTERLINE OF THE DEDICATED SPACE. |
| | |
| | 5) P1 & P2: HOT WATER NOT TEMPERED WATER IS REQUIRED AT |
| | THE BREAKROOM SINK- SEC. 607.1 FBC P. |
| | |
| | 6) P2: DEDICATED SHUTOFF VALVE ARE REQUIRED FOR THE |
| | COLD WATER LINES TO THE WATER HEATERS. THE VALVES SHALL |
| | NOT INTERFERE OR CAUSE A DISRUPTION OF THE COLD WATER |
| | SUPPLY TO THE REMAINDER OF THE COLD WATER SYSTEM- SEC. |
| | 503.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |