| Plan Review Notes For Permit 21111081 |
| Permit Number |
21111081 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-12-08 09:13:39 | 1) WITHOUT KNOWING THE FLOW OF THIS BUSINESS I AM | | | CONSIDERING THE MEETING AREA AS A CONFERENCE ROOM AREA. | | | THIS WOULD BE CALCULATED DIFFERENTLY FROM THE BREAK | | | AREA. THE SUBMITTED OUTDOOR AIR CALCULATIONS USE THE | | | SAME OCCUPANT DENSITY, PEOPLE OUTDOOR AIRFLOW RATE IN | | | BREATHING ZONE AND AREA OUTDOOR AIRFLOW RATE IN | | | BREATHING ZONE FOR ALL THREE AREAS WHICH IS THE OFFICE | | | SPACES OCCUPANCY DENSITY. IF THE ENTIRE AREA IS TO BE | | | CONSIDERED OFFICE SPACE THEN PLEASE RELABEL THE DRAWING | | | TO REFLECT THIS. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE INTRODUCED | | | TO THIS ENTIRE TENANT SPACE SINCE YOU ARE USING | | | MINI-SPLITS. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|