| 2022-01-13 17:15:04 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21111063 |
| | |
| | NOTE: |
| | THERE ARE TWO SEPARATE BUILDINGS IN THIS PARCEL. TWO |
| | SEPARATE PERMIT APPLICATIONS WERE GENERATED TO AVOID |
| | CONFLICTS/CONFUSIONS AND ALLOW PROPER INSPECTIONS. THIS |
| | PERMIT #21111063 IS FOR THE APT/GARAGE. AND PERMIT |
| | #21110619 IS FOR THE MAIN HOUSE. PLEASE SUBMIT ONLY THE |
| | INFORMATION PERTINENT TO THE APT/GARAGE . |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- PROVIDE FLOOR PLAN OR SKETCH CLEARLY IDENTIFYING THE |
| | ROOMS WHERE WINDOWS/DOORS ARE GOING TO BE REPLACED. FOR |
| | EXAMPLE: BEDROOM, LIVING AREA, ETC. THIS IS REQUIRED TO |
| | IDENTIFY THE BEDROOMS AND VERIFY COMPLIANCE WITH THE |
| | EGRESS REQUIREMENTS. |
| | NOTE: CLEARLY SPECIFY SIZE AND TYPE OF EXISTING WINDOW |
| | AND SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 |
| | FBC-EXISTING BUILDING. |
| | COORDINATE WINDOWS/DOORS SHOWN ON THE FLOOR PLAN WITH |
| | WINDOWS/DOORS SHOWN ON THE ENGINEER WINDOW/DOOR |
| | SCHEDULE SUBMITTED TO AVOID CONFLICTS/DELAYS. |
| | |
| | ****TO FACILITATE THE FLOOR PLANS REQUIREMENT, |
| | CONTRACTOR MAY COPY PLANS SUBMITTED FOR THE MAIN HOUSE |
| | AND GARAGE/APT BUILDING FOR REFERENCE. CLEARLY |
| | KEY/IDENTIFY EACH WINDOW AND DOOR WITH WINDOW/DOOR |
| | SCHEDULE SUBMITTED. |
| | |
| | 2- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW |
| | OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE |
| | REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT |
| | A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE |
| | FINISHED FLOOR. CLEARLY SPECIFY IF THERE ARE ANY |
| | WINDOWS WHERE THE WINDOW SILL IS LESS THAN 24" ABOVE |
| | THE FINISH FLOOR. SEE SEC. 702.4 FBC-EXISTING BUILDING |
| | CODE |
| | |
| | 3- ENGINEER WINDOW/DOOR SCHEDULE SUBMITTED IS |
| | INCOMPLETE: |
| | CLEARLY SPECIFY TYPE OF WINDOW AND WINDOW DIMENSIONS |
| | (WIDTH X HEIGHT) NOT JUST THE OPENING ROUGH AREA. SEC. |
| | 107.2.1 CITY AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE. |
| | |
| | 4- PROVIDE COMPLETE FLORIDA PRODUCT APPROVALS. PRODUCT |
| | APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT |
| | SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL |
| | STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| | NOTE: SUBMIT COMPLETE FLORIDA PRODUCT APPROVAL (COVER |
| | PAGE AND INSTALLATION DRAWINGS) IN ONE PDF FOR EACH |
| | WINDOW/DOOR TYPE. DON?T SPLIT INTO TWO OR MORE SEPARATE |
| | FILES. |
| | |
| | ALSO, IT LOOKS LIKE SOME PRODUCT APPROVALS WERE |
| | SUBMITTED TWICE. PLEASE DELETE ANY REPEATED PRODUCT |
| | APPROVAL TO AVOID CONFLICTS/DELAYS. |
| | |
| | 5- IF WINDOW REPLACEMENT INCLUDES WINDOW MULLIONS, THEN |
| | PROVIDE PRODUCT APPROVAL FOR SUCH WINDOW MULLIONS. |
| | (NOTE: NEED TO SPECIFY MULLION SIZE TO AVOID |
| | DELAYS/CONFLICTS). |
| | |