| 2022-02-04 11:52:55 | THE REVIEW COMMENTS FROM THE PRIOR REVIEW HAVE NOT BEEN | | | ADDRESSED. PLEASE PROVIDED DETAIL TO COMPLIANCE WITH | | | CODE REQUIREMENT FOR PANIC HARDWARE TO BE INSTALLED IN | | | EGRESS DOORS FROM ASSEMBLY SPACE. | | | | | | FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN | | | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER | | | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE | | | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER | | | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE | | | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR | | | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE | | | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A | | | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN | | | UNLOCKED WHEN THE BUILDING IS OCCUPIED, HOWEVER EGRESS | | | DOORS FROM THE ASSEMBLY SPACE ITSELF SHALL BE EQUIPPED | | | WITH PANIC HARDWARE. | | | | | | PLEASE INDICATE ON DOOR SCHEDULE/SPEC SHEET THE TYPE | | | AND OPERATION OF PANIC HARDWARE FOR THE EGRESS DOORS TO | | | BE INSTALLED. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|