| Plan Review Notes For Permit 21111015 |
| Permit Number |
21111015 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-07 08:20:54 | PLUMBING REVIEW AUDIT | | | | | | PERMIT 21111015 | | | | | | P601 - PER V7 FBC P - 901.2 - TRAP SEAL PROTECTION - | | | MOP SINK DETAIL DOES NOT SHOW A TRAP. ALL P-TRAPS SHALL | | | BE VENTED. | | | | | | P601 PER V7 FBC P - 607.1.1 - DETAIL FOR TANKLESS HOT | | | WATER SHOULD SHOW A LIMITING DEVICE OTHER THAN THE | | | THERMOSTAT FOR THE WATER HEATER. THERMOSTATIC MIXING | | | DEVICE IS TYPICAL. | | | | | | | | | AUDIT PERRORMED BY: | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|