Notes
Date Text
2021-12-09 11:48:101ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21111013
 12/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.3- FBC ACC COMPLIANCE DETAILS REQUIRED FOR
 THE NEW BATHROOMS 844, 861, 864, & 865. PLEASE PROVIDE
 ENLARGED, DIMENSIONED DRAWINGS AND ELEVATION VIEWS
 SHOWING:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 2) A3.3- FBC ACC COMPLIANCE DETAILS FOR ROOMS 806, 846,
 857:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SINKS AND APPLIANCES- SECTION 606.2.
 B) HEIGHTS OF THE SINK RIMS OR COUNTER SURFACES FROM
 THE FINISHED FLOORS- SECTION 606.3.
 C) HEIGHTS OF COFFEE DISPENSER CONTROLS AND OTHER
 COUNTERTOP APPLIANCE CONTROLS- SECTION 308.
 D) OPERABLE PARTS COMPLIANCE FOR APPLIANCES- 804.6.2.
 D) PLACE A NOTE TO INDICATE THE REFRIGERATOR/FREEZER
 SHALL HAVE AT LEAST 50 PERCENT OF THE FREEZER SPACE 54
 INCHES MAXIMUM ABOVE THE FINISH FLOOR- 804.6.6.
  
 3) P1.1 & P1.2: VENTS MISSING FOR THE WATER CLOSETS
 WC-2 AND THE EFD IN ROOM 863- SECTION 909, 910, 911, &
 912 FBC P.
  
 4) P2.2: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO COFFEE
 DISPENSERS, DISHWASHER, ICE MAKERS ETC. SECTIONS 604.9
 & 608.3 FBC P. LIST THE MAKES AND MODELS OF THE
 BACKFLOW DISPENSERS- TABLE 608.3 FBC P.
  
 5) P3.1: SHOW THE HEIGHT OF THE SPOUT FOR THE STANDING
 PERSON'S DRINKING FOUNTAIN- SECTION 602.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER