| 2021-12-02 10:56:00 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21111013 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M4.1: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS BASED ON FBC M 403.3.1.1 AND TABLE |
| | 403.3.1.1. THE NOTE UNDER THE VENTILATION CALCULATIONS |
| | STATES THE SEATING PLAN WAS USED FOR THE PEOPLE COUNT. |
| | FBC M 403.3.1.1 DOES NOT ALLOW THIS AND STATES YOU MUST |
| | USE TABLE 403.3.1.1 FOR THE OCCUPANT COUNTS. |
| | |
| | 2) SHEET M2.3: VAV-8-11 INDICATES A TOTAL OF 1000 CFM |
| | OF SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART |
| | INDICATES THAT VAV-8-11 SUPPLIES ONLY 900 CFM OF SUPPLY |
| | AIR. FBC 107.2.1 |
| | |
| | 3) SHEET M2.3: VAV-8-15 INDICATES A TOTAL OF 775 CFM OF |
| | SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART INDICATES |
| | THAT VAV-8-15 SUPPLIES ONLY 675 CFM OF SUPPLY AIR. FBC |
| | 107.2.1 |
| | |
| | 4) SHEET M2.3: VAV-8-17 INDICATES A TOTAL OF 1350 CFM |
| | OF SUPPLY AIR. SHEET M4.1 VAV BOX SCHEDULE CHART |
| | INDICATES THAT VAV-8-17 SUPPLIES ONLY 500 CFM OF SUPPLY |
| | AIR. FBC 107.2.1 |
| | |
| | 5) SHEET M2.3: THEE ARE 2 VAV-8-20. THEY BOTH SUPPLY |
| | DIFFERENT CFM?S PLEASE RENAME ONE OR ADD A NOTE |
| | CLARIFYING THE DRAWING DOES HAVE 2 VAV-8-20. FBC |
| | 107.2.1 |
| | |
| | 6) SHEETS M2.3 AND M2.2: VAV-8-26 DOES NOT HAVE THE |
| | CFM?S AT THE GRILLES. FBC 107.2.1 |
| | |
| | 7) PLEASE IDENTIFY VAV-8-25 ON THE DRAWING AS IT IS NOT |
| | WHERE SHEET M0.1 INDICATES. FBC 107.2.1 |
| | |
| | 8) PLEASE PROVIDE INFORMATION ON THE EXHAUST FAN THAT |
| | INDICATE THE HOUSE EXHAUST FAN ON THE ROOF HAS THE |
| | EXTRA CFM?S FOR THIS ADDITIONAL LOAD OF 600 CFM?S. FBC |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |