| Plan Review Notes For Permit 21111011 |
| Permit Number |
21111011 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-09 07:57:07 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21111011 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A SIGN ON THE WALL STATING THAT THE DOORS ARE TO | | | REMAIN OPEN DURING OPERATION HOURS DOES NOT MEET THE | | | INTENT OF THE CODE SECTION BELOW. LOUVERS SIZED FOR THE | | | SYSTEM OUTDOOR AIR REQUIREMENTS OF FBC M TABLE | | | 403.3.1.1 AND ARE TIED IN TO THE FAN OPERATION WOULD | | | MEET THE INTENT OF THE CODE SECTION BELOW | | | | | | FBC M 403.3.1.1- THE VENTILATION SYSTEM SHALL BE | | | DESIGNED TO SUPPLY THE REQUIRED RATE OF VENTILATION AIR | | | CONTINUOUSLY DURING THE PERIOD THE BUILDING IS | | | OCCUPIED, EXCEPT AS OTHERWISE STATED IN OTHER | | | PROVISIONS OF | | | THE CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|