Plan Review Notes
Plan Review Notes For Permit 21111011
Permit Number 21111011
Review Stop M
Sequence Number 2
Notes
Date Text
2022-03-09 07:57:072ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21111011
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SIGN ON THE WALL STATING THAT THE DOORS ARE TO
 REMAIN OPEN DURING OPERATION HOURS DOES NOT MEET THE
 INTENT OF THE CODE SECTION BELOW. LOUVERS SIZED FOR THE
 SYSTEM OUTDOOR AIR REQUIREMENTS OF FBC M TABLE
 403.3.1.1 AND ARE TIED IN TO THE FAN OPERATION WOULD
 MEET THE INTENT OF THE CODE SECTION BELOW
  
 FBC M 403.3.1.1- THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO SUPPLY THE REQUIRED RATE OF VENTILATION AIR
 CONTINUOUSLY DURING THE PERIOD THE BUILDING IS
 OCCUPIED, EXCEPT AS OTHERWISE STATED IN OTHER
 PROVISIONS OF
 THE CODE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  