| Plan Review Notes For Permit 21111011 |
| Permit Number |
21111011 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-06 13:29:57 | 01/06/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON SHEET P1.1; | | | | | | A. IT MENTIONS THE STORM CONTINUING ON THE CIVIL PLANS | | | AND NO PAGE FOR CIVIL PROVIDED. WOULD YOU PLEASE | | | PROVIDE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | B. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM | | | FOR THE STORM PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.5.1.3 (13) COMMERCIAL PLUMBING. | | | | | | C. WOULD YOU PLEASE SHOW A CLEANOUT FOR THE STORM PER | | | THE 202 FBC SEC. 1101.8CLEANOUTS REQUIRED. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|