| 2022-01-06 07:31:24 | 01/06/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET A-4.00; |
| | |
| | A. ON DETAIL #6, THE URINAL PARTITION SHALL PROVIDE |
| | PRIVACY PARTITIONS SHALL BEGIN AT A HEIGHT NOT GREATER |
| | THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60 INCHES |
| | ABOVE THE FINISHED FLOOR SURFACE PER THE 2020 FBC SEC. |
| | P 405.3.5 URINAL PARTITIONS. |
| | |
| | B. FOR THE MIRRORS, PLEASE LABEL THE REFLECTIVE PART OF |
| | THE MIRROR THAT NEEDS TO BE 40" TO THE REFLECTIVE SIDE |
| | PER THE 2020 FBC ACC SEC. 603.3. SHOW IT ON DETAIL #4 |
| | IN THE OPEN AREA AS WELL. |
| | |
| | C. ON THE REAR WALL GRAB BAR, THE REAR NEEDS TO BE |
| | MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES |
| | AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.2 REAR |
| | WALL. THE TOILET SAYS 17 INCHES FROM THE WALL, WHICH IS |
| | NOT AN ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18 |
| | INCHES TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE |
| | INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC |
| | ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. WOULD YOU PLEASE SHOW THE 42 INCHES FOR GRAB BAR PER |
| | THE 2020 ACC 604.5.1SIDE WALL. |
| | |
| | E. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE |
| | DIMENSIONS FOR THE LAVATORY, WATER CLOSET, TURNING |
| | CIRCLE, URINAL, AND LAV PER THE 2020 FBC ACC SEC. |
| | 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | 2. ON SHEET A-4.02, WOULD YOU PLEASE SHOW THE CLEAR |
| | FLOOR SPACE FOR THE BREAK SINK PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | 3. ON SHEET A-6.02, THERE IS A SCUPPER. WOULD YOU |
| | PLEASE PROVIDE DETAIL FOR THE ALLOWABLE SIZE PER THE |
| | 2020 FBC SEC? P 1106.5 PARAPET WALL SCUPPERS. |
| | |
| | 4. ON SHEET E1.3, IT SHOWS TWO SINKS, BUT ON THE P2.3, |
| | THERE IS ONLY ONE SINK SHOWN. WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 5. ON SHEET P0.1; |
| | |
| | A. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF |
| | FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE |
| | OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER |
| | OF FIXTURES. |
| | |
| | B. IN THE ABOVE OCCUPANT LOAD, A DRINKING FOUNTAIN MAY |
| | BE REQUIRED FOR THIS ESTABLISHMENT; IF SO, WOULD YOU |
| | PLEASE PROVIDE THE FOLLOWING; |
| | A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3. |
| | |
| | C. IT SHALL BE ACCESSIBLE IN ACCORDANCE WITH 2020 FBC |
| | ACC SEC. 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND |
| | DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE |
| | FOR A FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE |
| | DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR |
| | SPACE AND PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, SPOUT LOCATIONS PER THE 2020 FBC ACC SEC. 306, |
| | 307, & 602.2, COMPLIANCE WITH 2020 FBC ACC SEC. 307.2 |
| | PROTRUSION LIMITS. |
| | |
| | D. PLEASE SHOW ON ISOMETRIC SANITARY AND WATER PER THE |
| | 2020 FBC SEC. PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 6. ON SHEET P2.3; |
| | |
| | A. IT SHOWS A GAS GRILL ON THE ROOF. WILL THIS BE A |
| | TANK-TYPE OR CITY SYSTEM? WOULD YOU PLEASE CLARIFY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 7. WOULD YOU PLEASE SHOW THE INDIRECT DRAIN ELEVATOR |
| | PIT ON THE ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 8. ON SHEET P3.3, PLEASE SHOW CLEANOUT AT THE BOTTOM OF |
| | EACH RISER PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS |
| | REQUIRED. |
| | |
| | 9. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS |
| | FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS WHERE |
| | APPLICABLE. PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS |
| | FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. |
| | 107.2.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |