Plan Review Notes
Plan Review Notes For Permit 21111010
Permit Number 21111010
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-06 07:31:2401/06/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET A-4.00;
  
 A. ON DETAIL #6, THE URINAL PARTITION SHALL PROVIDE
 PRIVACY PARTITIONS SHALL BEGIN AT A HEIGHT NOT GREATER
 THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60 INCHES
 ABOVE THE FINISHED FLOOR SURFACE PER THE 2020 FBC SEC.
 P 405.3.5 URINAL PARTITIONS.
  
 B. FOR THE MIRRORS, PLEASE LABEL THE REFLECTIVE PART OF
 THE MIRROR THAT NEEDS TO BE 40" TO THE REFLECTIVE SIDE
 PER THE 2020 FBC ACC SEC. 603.3. SHOW IT ON DETAIL #4
 IN THE OPEN AREA AS WELL.
  
 C. ON THE REAR WALL GRAB BAR, THE REAR NEEDS TO BE
 MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES
 AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.2 REAR
 WALL. THE TOILET SAYS 17 INCHES FROM THE WALL, WHICH IS
 NOT AN ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18
 INCHES TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE
 INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC
 ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW THE 42 INCHES FOR GRAB BAR PER
 THE 2020 ACC 604.5.1SIDE WALL.
  
 E. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE
 DIMENSIONS FOR THE LAVATORY, WATER CLOSET, TURNING
 CIRCLE, URINAL, AND LAV PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 2. ON SHEET A-4.02, WOULD YOU PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE BREAK SINK PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 3. ON SHEET A-6.02, THERE IS A SCUPPER. WOULD YOU
 PLEASE PROVIDE DETAIL FOR THE ALLOWABLE SIZE PER THE
 2020 FBC SEC? P 1106.5 PARAPET WALL SCUPPERS.
  
 4. ON SHEET E1.3, IT SHOWS TWO SINKS, BUT ON THE P2.3,
 THERE IS ONLY ONE SINK SHOWN. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P0.1;
  
 A. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF
 FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER
 OF FIXTURES.
  
 B. IN THE ABOVE OCCUPANT LOAD, A DRINKING FOUNTAIN MAY
 BE REQUIRED FOR THIS ESTABLISHMENT; IF SO, WOULD YOU
 PLEASE PROVIDE THE FOLLOWING;
 A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3.
  
 C. IT SHALL BE ACCESSIBLE IN ACCORDANCE WITH 2020 FBC
 ACC SEC. 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND
 DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE AND PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, SPOUT LOCATIONS PER THE 2020 FBC ACC SEC. 306,
 307, & 602.2, COMPLIANCE WITH 2020 FBC ACC SEC. 307.2
 PROTRUSION LIMITS.
  
 D. PLEASE SHOW ON ISOMETRIC SANITARY AND WATER PER THE
 2020 FBC SEC. PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 6. ON SHEET P2.3;
  
 A. IT SHOWS A GAS GRILL ON THE ROOF. WILL THIS BE A
 TANK-TYPE OR CITY SYSTEM? WOULD YOU PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 7. WOULD YOU PLEASE SHOW THE INDIRECT DRAIN ELEVATOR
 PIT ON THE ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 8. ON SHEET P3.3, PLEASE SHOW CLEANOUT AT THE BOTTOM OF
 EACH RISER PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS
 REQUIRED.
  
 9. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS WHERE
 APPLICABLE. PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS
 FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR