| 2021-12-22 13:23:55 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21111010 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.3: OUTSIDE AIR CALCULATIONS: ROOM 101 |
| | RECEPTION MINIMUM OUTDOOR AIR REQUIRED IS 63 CFM. THE |
| | COLUMN NAMED MIN. OUTDOOR AIR PROVIDED STATES ONLY 54 |
| | CFM?S PROVIDE FOR THIS SPACE. PLEASE CORRECT TO SHOW AT |
| | LEAST THE MINIMUM REQUIRED. FBC M 403.3.1.1 AND FBC M |
| | TABLE 403.3.1.1 |
| | |
| | 2) THE LECTURE CLASSROOMS MUST BE CALCULATED USING FBC |
| | M 403.3.1.1 AND FBC M TABLE 403.3.1.1, THE OUTDOOR AIR |
| | SHOWN IN THE MINIMUM OUTDOOR AIR REQUIRED IS LOW FOR |
| | BOTH LECTURE CLASSROOMS. PLEASE SHOW THE REQUIRED |
| | MINIMUM CFM?S FOR THESE LECTURE CLASSROOMS. |
| | |
| | 3) SHEET M0.2: VAV-1 AND VAV-2 TOTAL CFM?S ARE REVERSED |
| | ACCORDING TO SHEET M1.1. |
| | |
| | 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| | TERMINATION LOCATION. FBC M 307 |
| | |
| | 5) SHEET M0.2: EF1.1 IS EXHAUSTING 400 CFM, SHEET M1.1 |
| | INDICATES IT IS EXHAUSTING 450 CFM. PLEASE BE |
| | CONSISTENT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |