2021-12-22 13:23:551ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21111010
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.3: OUTSIDE AIR CALCULATIONS: ROOM 101
 RECEPTION MINIMUM OUTDOOR AIR REQUIRED IS 63 CFM. THE
 COLUMN NAMED MIN. OUTDOOR AIR PROVIDED STATES ONLY 54
 CFM?S PROVIDE FOR THIS SPACE. PLEASE CORRECT TO SHOW AT
 LEAST THE MINIMUM REQUIRED. FBC M 403.3.1.1 AND FBC M
 TABLE 403.3.1.1
  
 2) THE LECTURE CLASSROOMS MUST BE CALCULATED USING FBC
 M 403.3.1.1 AND FBC M TABLE 403.3.1.1, THE OUTDOOR AIR
 SHOWN IN THE MINIMUM OUTDOOR AIR REQUIRED IS LOW FOR
 BOTH LECTURE CLASSROOMS. PLEASE SHOW THE REQUIRED
 MINIMUM CFM?S FOR THESE LECTURE CLASSROOMS.
  
 3) SHEET M0.2: VAV-1 AND VAV-2 TOTAL CFM?S ARE REVERSED
 ACCORDING TO SHEET M1.1.
  
 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC M 307
  
 5) SHEET M0.2: EF1.1 IS EXHAUSTING 400 CFM, SHEET M1.1
 INDICATES IT IS EXHAUSTING 450 CFM. PLEASE BE
 CONSISTENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  