| 2021-12-29 13:29:32 | NEW 2 STORY OFFICE BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A-0.30 - THE TABLE SHOWN ON THE DRAWING - |
| | UNDER "EGRESS AND TRAVEL" LAST COLUMN SHOWS "NO |
| | SPRINKLER AND 1 STORY" - PLEASE CLARIFY. |
| | |
| | 2) PLEASE SHOW WALL FINISH ON THE FINISH SCHEDULE FOR |
| | THE RESTROOM AND MOP SINK AREA TO COMPLY WITH FBC |
| | 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 3) PLEASE SHOW THE OCCUPANT LOAD FOR THE TRAINING ROOM |
| | - FBC 1004.4 |
| | |
| | 4) PLEASE SHOW THE DIAGONAL DISTANCE OF THE TRAINING |
| | ROOM AND THE DISTANCE BETWEEN THE 2 DOORS IN THE |
| | TRAINING ROOM - FBC 1007.1.1 |
| | |
| | 5) PLEASE SHOW THE USE FOR THE 2 FLOOR SPACE FBC |
| | CHAPTER 3 |
| | |
| | 6) PLEASE SHOW STAIR NUMBER 1 TO EXIT TO THE OUTSIDE OF |
| | THE BUILDING OR SHOW THE EGRESS TRAVEL DISTANCE FROM |
| | THE ROOF TOP TO THE EXIT DISCHARGE FBC TABLE 1017.2 - - |
| | - FBC 1023.1 GENERAL. |
| | INTERIOR EXIT STAIRWAYS AND RAMPS SERVING AS AN EXIT |
| | COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL COMPLY WITH |
| | THE REQUIREMENTS OF THIS SECTION. INTERIOR EXIT |
| | STAIRWAYS AND RAMPS SHALL BE ENCLOSED AND LEAD DIRECTLY |
| | TO THE EXTERIOR OF THE BUILDING OR SHALL BE EXTENDED TO |
| | THE EXTERIOR OF THE BUILDING WITH AN EXIT PASSAGEWAY |
| | CONFORMING TO THE REQUIREMENTS OF SECTION 1024, EXCEPT |
| | AS PERMITTED IN SECTION 1028.1. AN INTERIOR EXIT |
| | STAIRWAY OR RAMP SHALL NOT BE USED FOR ANY PURPOSE |
| | OTHER THAN AS A MEANS OF EGRESS AND A CIRCULATION PATH. |
| | |
| | 7) PLEASE SHOW THE FRONT DOOR TO SWING OUT - FBC |
| | 1010.1.2 |
| | |
| | 8) PLEASE SHOW THE ROOF TOP MECHANICAL SCREENING |
| | ATTACHMENT DETAILS TO COMPLY WITH THE WIND LOADS FBC |
| | 1609 |
| | |
| | 9) PLEASE SHOW THE ROOF TOP FRONT RAILING HEIGHT AND |
| | OPENING LIMITATIONS PER FBC SECTION 1015 |
| | |
| | 10) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE |
| | TOP AND BOTTOM (TOP HORIZONTAL AND BOTTOM SLOPE) - FBC |
| | 1014.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| | |
| | 11) PLEASE PROVIDE A SOIL REPORT AS SHOWN ON THE |
| | DRAWINGS. |
| | |
| | 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR |
| | DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS |
| | NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD. FBC WPB 107.3.4 |
| | |
| | 13) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR |
| | DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTIVE |
| | SURFACE" - FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 14) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB |
| | BARS MAXIMUM HEIGHT TO THE "TOP OF THE GRIPPING |
| | SURFACE" - FBC A 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | |
| | 15) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR |
| | GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER - |
| | FBC A 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 16) PLEASE SHOW THE ROOF TOP RESTROOM TO COMPLY WITH |
| | ACCESSIBILITY REQUIREMENTS - FBC A 213.1 |
| | |
| | 17) SEPARATE PERMITS ARE REQUIRED FOR - PARKING LOT, |
| | SITE LIGHTING, SIGNS, DUMPSTER, REAR WALK CANOPY, |
| | FENCING. EACH WITH ITS OWN APPLICATION FILLED OUT AND |
| | SENT TO THE PERMIT LIBRARIAN. |
| | |
| | 18 ) ITEMS SUCH AS ROOFING SYSTEMS, CANOPIES, ROOF TOP |
| | SCREENING, WINDOW AND DOOR PRODUCT APPROVALS MAY BE |
| | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON |
| | THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |