Plan Review Notes
Plan Review Notes For Permit 21111010
Permit Number 21111010
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-29 13:29:32NEW 2 STORY OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-0.30 - THE TABLE SHOWN ON THE DRAWING -
 UNDER "EGRESS AND TRAVEL" LAST COLUMN SHOWS "NO
 SPRINKLER AND 1 STORY" - PLEASE CLARIFY.
  
 2) PLEASE SHOW WALL FINISH ON THE FINISH SCHEDULE FOR
 THE RESTROOM AND MOP SINK AREA TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) PLEASE SHOW THE OCCUPANT LOAD FOR THE TRAINING ROOM
 - FBC 1004.4
  
 4) PLEASE SHOW THE DIAGONAL DISTANCE OF THE TRAINING
 ROOM AND THE DISTANCE BETWEEN THE 2 DOORS IN THE
 TRAINING ROOM - FBC 1007.1.1
  
 5) PLEASE SHOW THE USE FOR THE 2 FLOOR SPACE FBC
 CHAPTER 3
  
 6) PLEASE SHOW STAIR NUMBER 1 TO EXIT TO THE OUTSIDE OF
 THE BUILDING OR SHOW THE EGRESS TRAVEL DISTANCE FROM
 THE ROOF TOP TO THE EXIT DISCHARGE FBC TABLE 1017.2 - -
 - FBC 1023.1 GENERAL.
 INTERIOR EXIT STAIRWAYS AND RAMPS SERVING AS AN EXIT
 COMPONENT IN A MEANS OF EGRESS SYSTEM SHALL COMPLY WITH
 THE REQUIREMENTS OF THIS SECTION. INTERIOR EXIT
 STAIRWAYS AND RAMPS SHALL BE ENCLOSED AND LEAD DIRECTLY
 TO THE EXTERIOR OF THE BUILDING OR SHALL BE EXTENDED TO
 THE EXTERIOR OF THE BUILDING WITH AN EXIT PASSAGEWAY
 CONFORMING TO THE REQUIREMENTS OF SECTION 1024, EXCEPT
 AS PERMITTED IN SECTION 1028.1. AN INTERIOR EXIT
 STAIRWAY OR RAMP SHALL NOT BE USED FOR ANY PURPOSE
 OTHER THAN AS A MEANS OF EGRESS AND A CIRCULATION PATH.
  
 7) PLEASE SHOW THE FRONT DOOR TO SWING OUT - FBC
 1010.1.2
  
 8) PLEASE SHOW THE ROOF TOP MECHANICAL SCREENING
 ATTACHMENT DETAILS TO COMPLY WITH THE WIND LOADS FBC
 1609
  
 9) PLEASE SHOW THE ROOF TOP FRONT RAILING HEIGHT AND
 OPENING LIMITATIONS PER FBC SECTION 1015
  
 10) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE
 TOP AND BOTTOM (TOP HORIZONTAL AND BOTTOM SLOPE) - FBC
 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 11) PLEASE PROVIDE A SOIL REPORT AS SHOWN ON THE
 DRAWINGS.
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD. FBC WPB 107.3.4
  
 13) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTIVE
 SURFACE" - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 14) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB
 BARS MAXIMUM HEIGHT TO THE "TOP OF THE GRIPPING
 SURFACE" - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 15) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER -
 FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 16) PLEASE SHOW THE ROOF TOP RESTROOM TO COMPLY WITH
 ACCESSIBILITY REQUIREMENTS - FBC A 213.1
  
 17) SEPARATE PERMITS ARE REQUIRED FOR - PARKING LOT,
 SITE LIGHTING, SIGNS, DUMPSTER, REAR WALK CANOPY,
 FENCING. EACH WITH ITS OWN APPLICATION FILLED OUT AND
 SENT TO THE PERMIT LIBRARIAN.
  
 18 ) ITEMS SUCH AS ROOFING SYSTEMS, CANOPIES, ROOF TOP
 SCREENING, WINDOW AND DOOR PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.