| Plan Review Notes For Permit 21110999 |
| Permit Number |
21110999 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-14 13:30:03 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. [THE DIMENSIONS AND WEIGHT OF THE | | | GENERATOR IN THE PAD ENGINEERING IS MORE THAN THE | | | GENERATOR SHOWN PAGE 4 OF THE GENERATOR | | | SPECIFICATIONS.] THE GENERATOR PAD CALCULATIONS ARE FOR | | | A GENERATOR THAT WEIGHS 850 POUNDS. THE SPECIFICATIONS | | | FOR THE 22KW GENERAC GENERATOR HAS THE UNIT'S WEIGHT AS | | | 466 POUNDS. FBC AMENDMENTS 107.2.1 | | | | | | 2) RESOLVED. | | | | | | 3) RESOLVED. |
|