| 2022-02-24 15:02:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) THE FOLLOWING EQUIPMENT NEEDS TO SHOW THE LISTING |
| | FOR THE EQUIPMENT |
| | |
| | INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT SHALL |
| | BE INSTALLED AND USED IN ACCORDANCE WITH ANY |
| | INSTRUCTIONS INCLUDED |
| | IN THE LISTING OR LABELING. |
| | LISTING. PRODUCT TESTING, EVALUATION, AND LISTING |
| | (PRODUCT CERTIFICATION) SHALL BE PERFORMED BY |
| | RECOGNIZED QUALIFIED ELECTRICAL |
| | TESTING LABORATORIES AND SHALL BE IN ACCORDANCE WITH |
| | APPLICABLE PRODUCT STANDARDS RECOGNIZED AS ACHIEVING |
| | EQUIVALENT |
| | AND EFFECTIVE SAFETY FOR EQUIPMENT INSTALLED TO COMPLY |
| | WITH THIS CODE. |
| | |
| | SOLAR TREE, BATTERY RACK, BESS NEA CONTROLLER, BESS |
| | IMM, BESS CONTROL CABINET, BESS FIREWALL, 7580 PT |
| | OVERALL DIMS, OPTOS, OUTDOOR LIQUID COOLING RACK, |
| | AIR INFLATOR, INVERTER MPS125 EHV, NBDC, NBSK. |
| | |
| | 2) PAGE E-201 |
| | |
| | FAULT CURRENT CALCULATION 110.9, 110.10 |
| | OVERCURRENT PROTECTION FOR NBDC UNITS 500, 200 NEEDS TO |
| | SHOW SOMWHERE WHAT SIZE BREAKERS ARE BEING USED. |
| | LISTING FOR THE LINE SIDE TAP IN THE NBSK 112500S |
| | 110.3, 110.9, 110.10 |