| Plan Review Notes For Permit 21110952 |
| Permit Number |
21110952 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-07 08:35:31 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW CEILING HEIGHT ON THE FLOOR PLAN TO | | | COMPLY WITH FBC 1208.2 MINIMUM CEILING HEIGHTS. | | | OCCUPIABLE SPACES, HABITABLE SPACES AND CORRIDORS SHALL | | | HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES | | | (2286 MM) ABOVE THE FINISHED FLOOR. BATHROOMS, TOILET | | | ROOMS, KITCHENS, STORAGE ROOMS AND LAUNDRY ROOMS SHALL | | | HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET (2134 MM) | | | ABOVE THE FINISHED FLOOR. |
|