| 2021-11-29 18:55:45 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21110930 |
| | 11/29/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | 3. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. |
| | 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| | 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5. SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION |
| | OF THE TANKLESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 6. SUBMIT COPY OF THE SIZING TABLE USED IN THE DESIGN |
| | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF |
| | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2020 FBC FUEL GAS SEC. 402.3 OR 2020 FBC FUEL |
| | GAS RES. SEC. G2413.3 |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS/ENTIRE |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2408.1. |
| | 8. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND |
| | LABELED PER THE 2020 FBC FUEL GAS SEC.301.3 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2404.3. THE MANUFACTURER'S |
| | SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING |
| | EXHAUSTED BY THE DRYER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |