| Date |
Text |
| 2022-01-14 12:44:29 | ADDITION AND ALTERATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A0.0 IN PROJECT DATA - SHOWS THE FBC 2017 - |
| | THE CODE IN EFFECT IS FBC 2020 - PLEASE CORRECT. |
| | |
| | 2) THE ADDRESS SHOWN ON THE PLANS DOES NOT MATCH THE |
| | ADDRESS SHOWN ON THE BUILDING PERMIT APPLICATION - |
| | PLEASE CORRECT - THEY SHOULD MATCH. |
| | |
| | 3) PLEASE SHOW THE RESTROOM AND MOP SINK AREA WALL |
| | FINISH TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 4) PLEASE SHOW THE WIDTH OF THE RESTROOM HALLWAY |
| | (MARKED CORRIDOR) FBC WPB 107.2.1 |
| | |
| | 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK |
| | ROOFING - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED |
| | IN THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE |
| | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE |
| | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN |
| | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH |
| | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE |
| | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES ON THE |
| | PRODUCT APPROVALS. |
| | |
| | 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE LOCATION |
| | DIMENSIONS FOR THE TOILET PAPER HOLDER PER FBC A604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | |
| | 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE LOCATION |
| | DIMENSIONS AND THE LENGTH FOR THE TOILET REAR GRAB BAR |
| | FROM THE CENTER OF THE TOILET PER FBC A 604.5.2 REAR |
| | WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 8) ACCESSIBLE RESTROOM - PLEASE SHOW THE DIMENSION FOR |
| | THE MIRROR FROM THE FINISHED FLOOR TO THE BOTTOM OF THE |
| | "REFLECTING SURFACE" PER FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 9) ACCESSIBLE RESTROOM - DOORS CANNOT SWING INTO THE |
| | REQUIRED FIXTURE FLOOR SPACE - FBC A603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. EXCEPTIONS: 2. |
| | WHERE THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL |
| | USE AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS |
| | PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR |
| | SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR |
| | FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE. |
| | (PLEASE SHOW THE CLEAR FLOOR SPACE FOR THIS EXCEPTION) |
| | |
| | 10) PLEASE SHOW THE HEIGHT OF THE CUSTOMER SERVICE |
| | COUNTER TO COMPLY WITH FBC 904.4.1PARALLEL APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915 |
| | MM) MINIMUM LENGTH OF COUNTER. |
| | |
| | 11) PLEASE SHOW THE DIMENSIONS FOR THE EXTERIOR |
| | CUSTOMER SERVICE COUNTER (WALK UP) TO COMPLY WITH FBC |
| | 904.4.1PARALLEL APPROACH. |
| | A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915 |
| | MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM |
| | ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED |
| | FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915 |
| | MM) MINIMUM LENGTH OF COUNTER. |
| | |
| | 12) PLEASE SHOW THE REQUIRED DINING SEATING PER FBC |
| | 226.1 GENERAL. |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | |
| | 13) PLEASE SHOW THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | THE DUMPSTER AREA WHICH IS ON A SEPARATE PROPERTY. |
| | |
| | 13) PLEASE PROVIDE DETAILS FOR THE SCREEN ENCLOSURE OR |
| | STATE THAT THE SCREEN ENCLOSURE WILL BE ON A SEPARATE |
| | PERMIT. |
| | |