| 2022-03-04 14:37:05 | 2ND REVIEW FBC-2020 RES. | | | PERMIT-21110915 | | | 3/5/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS # 1 & 2 | | | FROM THE 1ST REVIEW ARE LISTED BELOW- PLEASE COMPLY. | | | | | | 1) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALL | | | MANUALS FOR THE TANKLESS WATER HEATERS, AND THE RANGE- | | | SECTIONS G2448.1, G2447.1 FBC RES. | | | | | | 2) P1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- | | | G2407.1. | | | | | | NEW COMMENT. | | | | | | 1) THE DRAWINGS INDICATE THE TANKLESS WATER HEATER WILL | | | BE INSTALLED LESS THAN THE MINIMUM REQUIRED CLEARANCE | | | OF 4 FT. FROM THE OPERABLE WINDOWS. PLEASE RELOCATE THE | | | UNIT IN ACCORDANCE WITH SECS. G2427.5 & G2427.8 FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|