Plan Review Notes
Plan Review Notes For Permit 21110915
Permit Number 21110915
Review Stop G
Sequence Number 2
Notes
Date Text
2022-03-04 14:37:052ND REVIEW FBC-2020 RES.
 PERMIT-21110915
 3/5/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS # 1 & 2
 FROM THE 1ST REVIEW ARE LISTED BELOW- PLEASE COMPLY.
  
 1) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALL
 MANUALS FOR THE TANKLESS WATER HEATERS, AND THE RANGE-
 SECTIONS G2448.1, G2447.1 FBC RES.
  
 2) P1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 G2407.1.
  
 NEW COMMENT.
  
 1) THE DRAWINGS INDICATE THE TANKLESS WATER HEATER WILL
 BE INSTALLED LESS THAN THE MINIMUM REQUIRED CLEARANCE
 OF 4 FT. FROM THE OPERABLE WINDOWS. PLEASE RELOCATE THE
 UNIT IN ACCORDANCE WITH SECS. G2427.5 & G2427.8 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  