Plan Review Notes
Plan Review Notes For Permit 21110915
Permit Number 21110915
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-14 15:38:57RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21110915
  
 NOTE:
 ADDITION SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- ALL ARCHITECTURAL DRAWINGS NEED ARCHITECT'S SEAL AND
 SIGNATURE AS REQUIRED BY SEC. 481 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 2- WINDOW "F" SPECIFIED ON THE WINDOW SCHEDULE ON SHEET
 A.07 AS AN EGRESS WINDOW DOESN'T COMPLY WITH EGRESS.
 40"X56" SINGLE HUNG WINDOW DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT OPENING. REVISE AS REQUIRED OR PROVIDE
 WINDOW CUT SHEET SHOWING COMPLIANCE. SEC. R310.2.1
 FBC-RESIDENTIAL.
  
 3- CONSTRUCTION OF NEW LOGGIA STRUCTURAL COLUMNS IS NOT
 CLEAR. EXTERIOR ELEVATIONS CALL FOR WOOD COLUMNS, WHILE
 STRUCTURAL PLANS CALL FOR MASONRY COLUMNS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. IF
 USING WOOD COLUMNS, THEN PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS INCLUDING WOOD TYPE, AND TOP AND
 BOTTOM CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL
  
 4- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1
 FBC-RESIDENTIAL.
  
 5- NEED COMPLETE BATHROOM WITH MAXIMUM POSSIBLE PRIVACY
 AND A DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS
 REQUIRED BY SEC. R320 FBC-RESIDENTIAL.
  
 6- REVISE/CLARIFY FRONT ENTRY WALL SECTION DETAIL
 07/S.02.
 A) THIS DETAIL SEEMS TO BE FOR AN INTERIOR BEARING WALL
 NOT FOR AN EXTERIOR WALL. REVISE AS REQUIRED TO SHOW
 INTERIOR AND EXTERIOR CONSTRUCTION MATERIALS,
 INSULATION, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REAR ELEVATION SPECIFIES VERTICAL SIDING ON REAR
 FACADE ONLY. PROVIDE DETAIL/SPECIFICATIONS FOR TYPE OF
 SIDING. WOOD OR CONCRETE?. CONCRETE SIDING REQUIRES
 PRODUCT APPROVAL. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- REVISE ROOF FASTENING SCHEDULE DETAIL 02/S.02.
 A)REVISE ROOF SHEATHING NAILING SPACING. ROOF SHEATHING
 NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 B)REVISE ROOF FASTENING ZONES DIAGRAM TO MATCH CURRENT
 DIAGRAM SHOWN ON CURRENT 2020 CODE. SEE FIGURE
 R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 8- LOGGIA SECTION DETAIL 05/S.01: THIS SECTION
 SPECIFIES 2X4 EXTERIOR FRAME WALL ABOVE NEW BIFOLDING
 GLASS DOOR. THERE IS NOT DETAIL 09/A.07. PROVIDE THIS
 DETAIL. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS SHOWING
 HOW COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH TYPE OF ROOFING SPECIFIED ON
 PLANS (TESLA PHOTOVOLTAIC ROOFING SYSTEM). CLEARLY
 SPECIFY WHICH METHOD OF SEC. R905.1.1.1 FBC-RESIDENTIAL
 IS GOING TO BE USED. AND PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY F.A.C. 61G20-3.001.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)TESLA PHOTOVOLTAIC ROOFING SYSTEM AND ANY OTHER ROOF
 SYSTEM TO BE USED.
 B)INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
 C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 D)16X8 FEET BIFOLD EXTERIOR DOORS AS SHOWN AT LOGGIA.
 E)ALL WINDOW TYPES SHOWN ON PLANS.
 F)SLIDING GLASS DOORS.
 G)FRENCH DOORS.
 H)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW
 BASED ON ALL SCOPE OF WORK SHOWN. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS,
 INCLUDING DESIGN PROFESSIONAL FEES OR PROVIDE COST
 BREAKDOWN, INCLUDING DESIGN PROFESSIONAL FEES FOR
 BUILDING OFFICIAL APPROVAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]