| 2022-04-05 09:27:38 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT | | | BEEN PERFORMED AT THIS TIME. PROVIDE COMPLETE PLANS AND | | | GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO | | | BE DONE PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | A SUB GAS PERMIT IS ON FILE BUT NO GAS INFORMATION HAS | | | BEEN SUBMITTED. | | | | | | A ISOMETRIC IS REQUIRED FOR GAS ISOMETRIC, ALL | | | APPLIANCES, IF OTHER APPLIANCES ARE IN THE SYSTEM SHOW | | | THEM, MANUFACTURE SPECIFICATION FOR EQUIPMENT AND | | | REGULATOR, TYPE OF GAS, TOTAL BTU'S, LONGEST RUN, | | | TABLES USED, PRESSURE OF GAS, SHOW AND LABEL SHUT OFF | | | VALVE, UNIONS, REGULATORS AND DRIP LEGS IF USED. | | | | | | |
|