Plan Review Notes
Plan Review Notes For Permit 21110872
Permit Number 21110872
Review Stop G
Sequence Number 1
Notes
Date Text
2022-01-25 09:24:56GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS ON FILE BUT NO GAS INFORMATION HAS
 BEEN SUBMITTED.
  
 NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME. THIS WILL HAVE THE GAS APPROVE FOR A SUB PERMIT,
 OR IF YOU DECIDED NOT TO, PLEASE PUT A NOTE ON THE GAS
 HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR
 THE GAS SYSTEM). AN N WILL BE PUT ON THIS REVIEW, WHICH
 STANDS FOR NOT REQUIRED, BUT A SUB PERMIT WON'T BE
 ISSUED ONCE A REVIEW IS DONE FOR THAT SUB PERMIT, SO
 PLEASE BE ADVISED ON THIS PROCEDURE.
  
 A ISOMETRIC IS REQUIRED FOR GAS ISOMETRIC, ALL
 APPLIANCES, IF OTHER APPLIANCES ARE IN THE SYSTEM SHOW
 THEM, MANUFACTURE SPECIFICATION FOR EQUIPMENT AND
 REGULATOR, TYPE OF GAS, TOTAL BTU'S, LONGEST RUN,
 TABLES USED, PRESSURE OF GAS, SHOW AND LABEL SHUT OFF
 VALVE, UNIONS, REGULATORS AND DRIP LEGS IF USED.
  
  