| Plan Review Notes For Permit 21110872 |
| Permit Number |
21110872 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-25 09:24:56 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT | | | BEEN PERFORMED AT THIS TIME. PROVIDE COMPLETE PLANS AND | | | GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO | | | BE DONE PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | A SUB GAS PERMIT IS ON FILE BUT NO GAS INFORMATION HAS | | | BEEN SUBMITTED. | | | | | | NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS | | | TIME. THIS WILL HAVE THE GAS APPROVE FOR A SUB PERMIT, | | | OR IF YOU DECIDED NOT TO, PLEASE PUT A NOTE ON THE GAS | | | HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR | | | THE GAS SYSTEM). AN N WILL BE PUT ON THIS REVIEW, WHICH | | | STANDS FOR NOT REQUIRED, BUT A SUB PERMIT WON'T BE | | | ISSUED ONCE A REVIEW IS DONE FOR THAT SUB PERMIT, SO | | | PLEASE BE ADVISED ON THIS PROCEDURE. | | | | | | A ISOMETRIC IS REQUIRED FOR GAS ISOMETRIC, ALL | | | APPLIANCES, IF OTHER APPLIANCES ARE IN THE SYSTEM SHOW | | | THEM, MANUFACTURE SPECIFICATION FOR EQUIPMENT AND | | | REGULATOR, TYPE OF GAS, TOTAL BTU'S, LONGEST RUN, | | | TABLES USED, PRESSURE OF GAS, SHOW AND LABEL SHUT OFF | | | VALVE, UNIONS, REGULATORS AND DRIP LEGS IF USED. | | | | | | |
|