| Plan Review Notes For Permit 21110869 |
| Permit Number |
21110869 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-23 14:27:14 | DISREGARD NOTES IN THIS REVIEW STOP - FIRE ENTERED IN | | | ERROR. LEM | | 2021-11-22 13:30:34 | SPECIFY DISTANCES FROM HVAC REGISTERS PER TABLE 8.3.2.5 | | | NFPA 13 | | | SPECIFY MAXIMUM DISTANCE BETWEEN HANGERS PER TABLE | | | 9.2.2.1 NFPA 13 | | | SPECIFY HOW HYDROSTATIC TESTING WILL BE CONDUCTED PER | | | SECTION 25.2.1 NFPA 13 | | | |
|