Plan Review Notes For Permit 21110859
Permit Number 21110859
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-16 09:54:40BATTERY STORAGE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) WIND DESIGN SHOWN - RISK CATEGORY II WIND SPEED
 167MPH - A RISK CATEGORY II REQUIRES A MINIMUM WIND
 SPEED OF 170MPH - PER FBC WPB SECTION 120.
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM.
  
 4) PRODUCT APPROVALS PROVIDED FOR THE EXTERIOR SWING
 DOORS AND OVERHEAD ROLLING DOOR SHOWS ATTACHMENT TO
 WOOD, METAL AND CONCRETE SUBSTRATE - THE ATTACHMENT TO
 FRP FRAMING WILL REQUIRE A SITE SPECIFIC ATTACHMENT
 DETAIL FROM A DESIGN PROFESSIONAL.
  
 5) PLEASE PROVIDE DETAILS FOR THE FOUNDATION SLAB FROM
 A DESIGN PROFESSIONAL - SHOW THE WIND DESIGN DATA USED
 ON THE SLAB DRAWINGS FBC 1603.1.4
  
 6) PLEASE SHOW THE DIMENSIONS FROM THE PROPERTY LINE
 AND OTHER BUILDINGS TO THE SHED - PLEASE PROVIDE A SITE
 PLAN SHOWING THE FOLLOWING INFORMATION 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 7) PLEASE SHOW THE BUILDING OCCUPANCY CLASSIFICATION
 PER FBC CHAPTER 3 - (H) OCCUPANCY CLASSIFICATION
 REQUIRES ADDITIONAL INFORMATION FBC 414.1.3 INFORMATION
 REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
  
  
  