Plan Review Notes
Plan Review Notes For Permit 21110859
Permit Number 21110859
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-27 09:38:36BATTERY STORAGE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) WIND DESIGN SHOWN - RISK CATEGORY II WIND SPEED
 167MPH - A RISK CATEGORY II REQUIRES A MINIMUM WIND
 SPEED OF 170MPH - PER FBC WPB SECTION 120.
  
 2) PLEASE SHOW THE EXTERIOR WALL PANEL ATTACHMENTS OR
 PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL
 FBC WPB 107.2.4
  
 3) PLEASE SHOW OR PROVIDE A STATEMENT FOR THE EXTERIOR
 WALL WEATHER PROTECTION - FBC 1403.2 WEATHER
 PROTECTION.
 EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER-RESISTANT EXTERIOR WALL ENVELOPE.
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS AND ROOFING SYSTEMS. - ALL PRODUCT APPROVALS NEED
 TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD - FBC WPB 107.3.4
  
 5) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY.
  
 6) PLEASE PROVIDE A SURVEY.
  
 7) PLEASE SHOW THE BUILDING OCCUPANCY CLASSIFICATION
 PER FBC CHAPTER 3 - (H) OCCUPANCY CLASSIFICATION
 REQUIRES ADDITIONAL INFORMATION FBC 414.1.3 INFORMATION
 REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
  
  
  