| 2022-04-01 15:55:52 | ELECTRIC REVIEW FAILED |
| | 1) METER IS INCORRECTLY DESCRIBE AS A 120/208 VOLT |
| | METER CAN. PLEASE DETAIL IT CORRECTLY. FBC 107.2 |
| | 2) RISER DIAGRAM DETAILS (2) SETS OF 500MCM RHU AS |
| | FEEDERS TO THE EXISTING 1000-AMP MDP. THESE CONDUCTORS |
| | ARE INADEQUATELY SIZED AS PER NEC 240.4(C). OVERCURRENT |
| | DEVICE OVER 800-AMPERES, THE AMPACITY OF CONDUCTORS IT |
| | PROTECTS SHALL BE EQUAL TO OR GREATER THE RATING OF THE |
| | OVERCURRENT DEVICE. PLEASE CORRECT WITH APPROPRIATELY |
| | SIZED CONDUCTORS. |
| | 2) THE RISER DIAGRAM DOES NOT DETAIL GROUND FAULT |
| | PROTECTION AS REQUIRED PER NEC 215.10 FOR DISCONNECTS |
| | OF 480 VOLT,1000AMP SYSTEMS. PLEASE DETAIL THAT THIS |
| | GROUND FAULT PROTECTION EXISTS OR WILL BE INSTALLED. |
| | 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION |
| | AND ENSURE EQUIPMENT RATING IS SUFFICIENT AS PER NEC |
| | 110.9. PLEASE INCLUDE A NOTE TO ENSURE LABLEING TO IS |
| | TO BE APPLIED ON EQUIPMENT AS PER NEC 110.24 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |