2022-02-10 10:57:32ELECTRIC PLAN REVIEW FAILED
 1) RISER DIAGRAM DOES NOT DETAIL WHICH IS NEW EQIPMENT
 AND EXISTING.IS THIS A NEW 400-AMP SERVICE. WORK SCOPE
 SUBMITTED DOES NOT INCLUDE A NEW ELECTRIC SERVICE.
 PLEASE DETAIL ALL EXISTING AND NEW ELECTRIC WORK
 CLEARLY. FBC 107.2
 2) ELECTRICAL LOAD CALCULATIONS APPEAR TO ONLY DETAIL
 ONE TANKLESS WATER HEATER. PLEASE PROVIDE CLARITY.
 AGAIN IS THIS NEW WIRING. PLEASE DETAIL ALL NEW AND
 EXISTING WIRING ACCURATLEY ON A FLOOR PLAN OR SITE
 PLAN. FBC 107.2
 3) PROVIDE DETAILS ON EXISTING WIRING AND PERMITTING AS
 WOULD BE REQUIRED FOR CAR CHARGERS, SERVICE, ETC.FBC
 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  