| 2021-12-01 17:30:16 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21110737 |
| | 12/1/21 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. PLEASE CLEARLY INDICATE WHAT TYPE OF FLUIDS WILL BE |
| | DISCHARGED INTO THE 2 FLOOR DRAINS IN THE GARAGE FLOOR. |
| | IT WOULD APEAR AS THOUGH THIS GARAGE WILL BE USED TO |
| | WASH OFF/ DETAIL THE VEHICLES. NO OIL, SAND OR OTHER |
| | SUBSTANCES SHALL BE DISHARGED INTO THE CITYS SANITARY |
| | SEWER SYSTEM. AN OIL AND SAND TRAP WOULD BE REQUIRED TO |
| | SEPERATE THIS. PLEASE CLEARIFY .WPB CODE OF ORDINANCES |
| | SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF |
| | DISCHARGE. (3)POLLUTANTS WHICH CREATE A FIRE OR |
| | EXPLOSION HAZARD IN THE WWF. PROHIBITED MATERIALS |
| | INCLUDE, BUT ARE NOT LIMITED TO, PETROLEUM OIL AND |
| | NON-BIODEGRADABLE CUTTING OIL, GASOLINE, KEROSENE, FUEL |
| | OIL, MOTOR OIL, NAPHTHA, BENZENE, TOLUENE, XYLENE, |
| | ETHERS, ALCOHOLS, KETONES, ALDEHYDES, PEROXIDES, |
| | CHLORATES, PERCHLORATES, BROMATES, CARBIDES, HYDRIDES, |
| | AND SULFIDES OR ANY OTHER SUBSTANCE WHICH THE CITY, THE |
| | STATE, OR ANY FEDERAL AGENCY HAS DETERMINED IS A FIRE |
| | HAZARD OR A HAZARD TO THE WWF. |
| | |
| | 2. FLOOR DRAINS REQUIRE TRAP PRIMMERS TO BE INSTALLED |
| | PER FBC P 2020 -901.2 |
| | |
| | 3. MINIMUM OF 1 SANITARY VENT SHALL BE RAN THROUGH THE |
| | ROOF PER FBC P 904.1 |
| | |
| | 4. PRESSURE VACUUM BREAKERS ARE REQUIRED FOR HOSE BIBBS |
| | AS PER FBC P608.16 |
| | |
| | 5. SEPERATE PERMIT REQUIRED FOR THE RELOCATION OF THE |
| | IRRIGATION AND THE WATER PURIFIER. WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. A SANITARY 2-WAY CLEAN OUT SHALL BE INSTALLED IN THE |
| | SEWER LINE WHERE THE SANITARY SEWER METS THE BUILDING |
| | MAIN DRAIN LINE ON THE EXTERIOR OF THE GARAGE.AS PER |
| | FBC P708.1.3 |
| | |
| | 7. HOW WILL HOT WATER BE SUPPLIED TO THE NEW SINK IN |
| | THE GARAGE? AS PER FBC P607.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |