2021-12-09 09:14:0116.4.4 ALTERATION OF BUILDINGS.
 16.4.4.1 WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION
 SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED OPERATIONAL
 AT ALL
 TIMES DURING ALTERATION.
 16.4.4.2 WHERE ALTERATION REQUIRES MODIFICATION OF A
 PORTION OF
 THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE SYSTEM
 SHALL BE
 KEPT IN SERVICE AND THE FIRE DEPARTMENT SHALL BE
 NOTIFIED.
 16.4.4.3 WHEN IT IS NECESSARY TO SHUT DOWN THE SYSTEM,
 THE AHJ
 SHALL HAVE THE AUTHORITY TO REQUIRE ALTERNATE MEASURES
 OF
 PROTECTION UNTIL THE SYSTEM IS RETURNED TO SERVICE.
 16.4.4.4 THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
 SYSTEM
 IS SHUT DOWN AND WHEN THE SYSTEM IS RETURNED TO
 SERVICE.
 16.4.4.5 ALL REQUIRED EXIT COMPONENTS SHALL BE
 MAINTAINED IN
 ACCORDANCE WITH THIS CODE AS DEEMED NECESSARY BY THE
 AHJ.
 16.4.4.6 FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION
 SHALL BE
 MAINTAINED. NFPA 1