| Notes |
| Date |
Text |
| 2022-03-15 15:10:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MANUFACTURER'S SPECIFICATIONS THAT WERE | | | SUBMITTED ARE FOR A 26 KW BRIGGS AND STRATTON GENERATOR | | | THAT WEIGHS 625 LBS. THE ENGINEERING FOR THE GENERATOR | | | PAD DOES NOT HAVE A 26 KW B&S GENERATOR LISTED. SUBMIT | | | DOCUMENTS FOR MATCHING EQUIPMENT. FBC AMENDMENTS | | | 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 3) SEE SIGNATURE REVIEW COMMENTS. | | | | | 2022-02-07 09:47:56 | PERMIT IS FOR A GENERATOR INSTALL JLEAHY |
|