Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop M
Sequence Number 3
Notes
Date Text
2022-07-14 10:53:263RD REVIEW FMC
 PERMIT: 21110639
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-10; THE OUTDOOR AIR CALCULATIONS FOR THE
 POOL ROOM AREA SHOULD BE REVISED TO SHOW THE CORRECTED
 MAX. OCCUPANCY NO. OF PEOPLE FOR THE MULTIPURPOSE
 ASSEMBLY OCCUPANCY WHICH WOULD BE 99 TOTAL OCCUPANTS
 FOR THIS AREA OF THE BUSINESS. THIS WOULD REQUIRE 544
 CFM?S OF OUTDOOR AIR. AHU-1 IS ALSO BEING IDENTIFIED AS
 FOR THE POOL AREA BUT SHEET M-1 SHOWS THAT AHU-2 IS
 CONDITIONING THE POOL TABLE AREA. FBC 107.2.1
  
 2) THE OCCUPANCY CLASSIFICATION FOR THE OUTDOOR AIR
 CALCULATIONS ON M-3 AND M-10 ARE NOT THE SAME. THE
 OCCUPANCY CLASSIFICATION MUST BE THE SAME ON BOTH
 SHEETS. FMC 403.3.1.1
  
 3) SHEET M-10: THE NOTES TO THE TABLE AT THE TOP OF THE
 SHEET ARE CUT OFF. THE REVIEWER CANNOT READ THESE
 NOTES, PLEASE CORRECT THIS SO THE ENTIRE NOTES ARE
 READABLE. FBC 107.2.1
  
 4) SHEET M-10: THE COLUMN THAT ANSWERS THE QUESTION IS
 IAQP OA CFM LEVEL ACCEPTABLE FOR XYLENE IS NOT
 COMPLETED. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  