| 2022-07-14 10:53:26 | 3RD REVIEW FMC |
| | PERMIT: 21110639 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-10; THE OUTDOOR AIR CALCULATIONS FOR THE |
| | POOL ROOM AREA SHOULD BE REVISED TO SHOW THE CORRECTED |
| | MAX. OCCUPANCY NO. OF PEOPLE FOR THE MULTIPURPOSE |
| | ASSEMBLY OCCUPANCY WHICH WOULD BE 99 TOTAL OCCUPANTS |
| | FOR THIS AREA OF THE BUSINESS. THIS WOULD REQUIRE 544 |
| | CFM?S OF OUTDOOR AIR. AHU-1 IS ALSO BEING IDENTIFIED AS |
| | FOR THE POOL AREA BUT SHEET M-1 SHOWS THAT AHU-2 IS |
| | CONDITIONING THE POOL TABLE AREA. FBC 107.2.1 |
| | |
| | 2) THE OCCUPANCY CLASSIFICATION FOR THE OUTDOOR AIR |
| | CALCULATIONS ON M-3 AND M-10 ARE NOT THE SAME. THE |
| | OCCUPANCY CLASSIFICATION MUST BE THE SAME ON BOTH |
| | SHEETS. FMC 403.3.1.1 |
| | |
| | 3) SHEET M-10: THE NOTES TO THE TABLE AT THE TOP OF THE |
| | SHEET ARE CUT OFF. THE REVIEWER CANNOT READ THESE |
| | NOTES, PLEASE CORRECT THIS SO THE ENTIRE NOTES ARE |
| | READABLE. FBC 107.2.1 |
| | |
| | 4) SHEET M-10: THE COLUMN THAT ANSWERS THE QUESTION IS |
| | IAQP OA CFM LEVEL ACCEPTABLE FOR XYLENE IS NOT |
| | COMPLETED. FMC 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |