| Date |
Text |
| 2022-03-17 12:11:40 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110639 |
| | 3/17/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS #1, 5, & 9 FROM |
| | THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES |
| | FOR CLARIFICATION. |
| | |
| | 1) SHEETS A.101, LS100 & P SHEETS: PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC |
| | P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES. THE CURRENT PLAN INDICATES |
| | A DEFICIENCY OF TWO WATER CLOSETS EACH FOR MALE AND |
| | FEMALE USE- (OCC. LOAD 168/2= 84 MALE AND FEMALE, 1 WC |
| | PER 40). AND TWO LAVATORIES EACH FOR MALE AND FEMALE |
| | USE- (1 PER 75). PLEASE NOTE THAT SEPARATE FACILITIES |
| | ARE REQUIRED FOR EACH SEX AND THE FIXTURES IN THE |
| | UNISEX RESTROOM CANNOT CONTRIBUTE TO THE NUMBER OF |
| | FIXTURES REQUIRED FOR MALE AND FEMALE USE BECAUSE IT IS |
| | NOT A SINGLE USER UNISEX RESTROOM- SECS. 403.1.2, |
| | 403.2, & 403.2.1 FBC P. I HAVE FORWARDED THE OWNER'S |
| | LETTER TO THE BUILDING OFFICIAL ROBERT BROWN, HOWEVER |
| | PLEASE NOTE THAT THE OCCUPANT LOAD OF 168 INDICATED IN |
| | THE LETTER IS NOT CONSISTENT WITH THE RESUBMITTED PLANS |
| | WHICH NOW INDICATES 147 ON SHEETS T.100 AND LS.100. THE |
| | REDUCTION IN OCCUPANT LOAD DID NOT CHANGE THE NUMBER OF |
| | PLUMBING FIXTURES REQUIRED PER TABLE 403.1 FBC P. |
| | |
| | 5) P-1 & P-4: THE CLEAR WATER WASTE DRAINAGE FROM THE |
| | BAR AREAS INCLUDING HAND SINKS, FLOOR DRAINS AND FLOOR |
| | SINKS BELOW ICE BINS, COOLERS, GLASS WASHERS ETC. SHALL |
| | NOT DRAIN INTO THE GREASE WASTE LINE AND INTERCEPTOR- |
| | SEC. 1003.3.1 FBC P. PLEASE CORRECT THE PLANS. THE |
| | RESUBMITTED PLUMBING PLANS INDICATE DISHWASHERS IN THE |
| | BARS 100 & 106, AND THE EQUIPMENT SCHEDULE (A103) |
| | INDICATES PIZZA MAKING EQUIPMENT BEHIND THE BARS. THE |
| | DRAINAGE FROM THE DISHWASHERS SHALL BE ROUTED TO THE |
| | GREASE WASTE LINE- SEC. 1003.3.1 FBC P. THE DRAINAGE |
| | FROM THE HANDSINKS AND ICE BINS SHALL REMAIN CONNECTED |
| | TO THE SANITARY DRAIN. |
| | |
| | 9) A103, P1, P2, P4: SHOW THE DWV AND WATER SUPPLY |
| | PIPING FOR THE WASHING MACHINE IN THE KITCHEN- SEC. |
| | 406.2 FBC P. PLUMBING FOR THE WASHING MACHINE NOT |
| | PROVIDED |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |