2022-03-17 12:11:402ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110639
 3/17/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS #1, 5, & 9 FROM
 THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES
 FOR CLARIFICATION.
  
 1) SHEETS A.101, LS100 & P SHEETS: PROVIDE PLUMBING
 FIXTURE CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE CURRENT PLAN INDICATES
 A DEFICIENCY OF TWO WATER CLOSETS EACH FOR MALE AND
 FEMALE USE- (OCC. LOAD 168/2= 84 MALE AND FEMALE, 1 WC
 PER 40). AND TWO LAVATORIES EACH FOR MALE AND FEMALE
 USE- (1 PER 75). PLEASE NOTE THAT SEPARATE FACILITIES
 ARE REQUIRED FOR EACH SEX AND THE FIXTURES IN THE
 UNISEX RESTROOM CANNOT CONTRIBUTE TO THE NUMBER OF
 FIXTURES REQUIRED FOR MALE AND FEMALE USE BECAUSE IT IS
 NOT A SINGLE USER UNISEX RESTROOM- SECS. 403.1.2,
 403.2, & 403.2.1 FBC P. I HAVE FORWARDED THE OWNER'S
 LETTER TO THE BUILDING OFFICIAL ROBERT BROWN, HOWEVER
 PLEASE NOTE THAT THE OCCUPANT LOAD OF 168 INDICATED IN
 THE LETTER IS NOT CONSISTENT WITH THE RESUBMITTED PLANS
 WHICH NOW INDICATES 147 ON SHEETS T.100 AND LS.100. THE
 REDUCTION IN OCCUPANT LOAD DID NOT CHANGE THE NUMBER OF
 PLUMBING FIXTURES REQUIRED PER TABLE 403.1 FBC P.
  
 5) P-1 & P-4: THE CLEAR WATER WASTE DRAINAGE FROM THE
 BAR AREAS INCLUDING HAND SINKS, FLOOR DRAINS AND FLOOR
 SINKS BELOW ICE BINS, COOLERS, GLASS WASHERS ETC. SHALL
 NOT DRAIN INTO THE GREASE WASTE LINE AND INTERCEPTOR-
 SEC. 1003.3.1 FBC P. PLEASE CORRECT THE PLANS. THE
 RESUBMITTED PLUMBING PLANS INDICATE DISHWASHERS IN THE
 BARS 100 & 106, AND THE EQUIPMENT SCHEDULE (A103)
 INDICATES PIZZA MAKING EQUIPMENT BEHIND THE BARS. THE
 DRAINAGE FROM THE DISHWASHERS SHALL BE ROUTED TO THE
 GREASE WASTE LINE- SEC. 1003.3.1 FBC P. THE DRAINAGE
 FROM THE HANDSINKS AND ICE BINS SHALL REMAIN CONNECTED
 TO THE SANITARY DRAIN.
  
 9) A103, P1, P2, P4: SHOW THE DWV AND WATER SUPPLY
 PIPING FOR THE WASHING MACHINE IN THE KITCHEN- SEC.
 406.2 FBC P. PLUMBING FOR THE WASHING MACHINE NOT
 PROVIDED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  