Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop M
Sequence Number 2
Notes
Date Text
2022-04-05 08:31:492ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21110639
  
 CODES IN EFFECT:2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS
 INDICATING THAT THE KITCHEN HOOD DESIGN WILL NOT BE
 REVIEWED UNDER THIS PERMIT AS IT WILL REQUIRE A
 SEPARATE PERMIT AND PLAN REVIEW.
  
 2) COMMENT 2 FROM 1ST REVIEW: SHEET M-1 WITH A REVISION
 DATE OF 02/28/2022 STILL SHOWS 1 WATER CLOSET AND 2
 URINALS IN BATHROOM 111. EF-1 IS INDICATING 150 CFM OF
 EXHAUST WITH INTERMITTENT OPERATION. PLEASE SHOW THE
 REQUIRED EXHAUST FOR 3 FIXTURES IN BATHROOM 111. FMC
 TABLE 403.3.1.1.
  
 3) COMMENT 2 OF 1ST CYCLE REVIEW: SHEET M-10 PROVIDES 2
 CONTAMINANTS. ASHRAE 62.1 2016 TABLE C-3 SHOWS THERE
 ARE SEVERAL CONTAMINANTS TO CONSIDER. IF ASHRAE 62.1 IS
 TO BE USED PLEASE PROVIDE A COMPLETE DESIGN. FMC 403.2
 OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW RATE
 SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 403.3.
 EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL
 DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM
 DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF
 CONTAMINANTS FROM EXCEEDING THAT OBTAINABLE BY THE RATE
 OF OUTDOOR AIR VENTILATION DETERMINED IN ACCORDANCE
 WITH SECTION 403.3, THE MINIMUM REQUIRED RATE OF
 OUTDOOR AIR SHALL BE REDUCED IN ACCORDANCE WITH SUCH
 ENGINEERED SYSTEM DESIGN.
  
 4) PLEASE CORRECT THE MINIMUM OUTDOOR AIR CALCULATIONS
 FOR EACH USE OF SPACE PER FMC 403.3.1.1 THIRD SENTENCE
 AND TABLE 403.3.1.1 BEFORE THE IAQ CALCULATION CAN BE
 USED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  