| 2022-04-05 08:31:49 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21110639 |
| | |
| | CODES IN EFFECT:2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS |
| | INDICATING THAT THE KITCHEN HOOD DESIGN WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT AS IT WILL REQUIRE A |
| | SEPARATE PERMIT AND PLAN REVIEW. |
| | |
| | 2) COMMENT 2 FROM 1ST REVIEW: SHEET M-1 WITH A REVISION |
| | DATE OF 02/28/2022 STILL SHOWS 1 WATER CLOSET AND 2 |
| | URINALS IN BATHROOM 111. EF-1 IS INDICATING 150 CFM OF |
| | EXHAUST WITH INTERMITTENT OPERATION. PLEASE SHOW THE |
| | REQUIRED EXHAUST FOR 3 FIXTURES IN BATHROOM 111. FMC |
| | TABLE 403.3.1.1. |
| | |
| | 3) COMMENT 2 OF 1ST CYCLE REVIEW: SHEET M-10 PROVIDES 2 |
| | CONTAMINANTS. ASHRAE 62.1 2016 TABLE C-3 SHOWS THERE |
| | ARE SEVERAL CONTAMINANTS TO CONSIDER. IF ASHRAE 62.1 IS |
| | TO BE USED PLEASE PROVIDE A COMPLETE DESIGN. FMC 403.2 |
| | OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW RATE |
| | SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 403.3. |
| | EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL |
| | DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM |
| | DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF |
| | CONTAMINANTS FROM EXCEEDING THAT OBTAINABLE BY THE RATE |
| | OF OUTDOOR AIR VENTILATION DETERMINED IN ACCORDANCE |
| | WITH SECTION 403.3, THE MINIMUM REQUIRED RATE OF |
| | OUTDOOR AIR SHALL BE REDUCED IN ACCORDANCE WITH SUCH |
| | ENGINEERED SYSTEM DESIGN. |
| | |
| | 4) PLEASE CORRECT THE MINIMUM OUTDOOR AIR CALCULATIONS |
| | FOR EACH USE OF SPACE PER FMC 403.3.1.1 THIRD SENTENCE |
| | AND TABLE 403.3.1.1 BEFORE THE IAQ CALCULATION CAN BE |
| | USED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |