Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop G
Sequence Number 2
Notes
Date Text
2022-03-17 13:12:442ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110639
 3/17/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS # FROM THE 1ST
 REVIEW REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) SHEETS P2 & P4: PROVIDE COMBUSTIONS AIR CALCULATIONS
 FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SEC. 304.1 FBC FG. THE ENGINEER?S
 RESPONSE LETTER REFERS TO M1 FOR THE CALCULATIONS. M1
 INDICATES 266 CFMS OF MECHANICALLY SUPPLIED COMBUSTION
 AIR TO IS TO BE PROVIDED BY THE MAKEUP AIR FAN FOR THE
 KITCHEN EXHAUST HOODS. REFER TO SHEET M-7 WHICH SHOWS
 2320 CFMS OF MAKE UP AIR IS DEDICATED AS REPLACEMENT
 AIR FOR THE HOOD EXHAUST SYSTEM 1 WHICH IS SIZED AT A
 GREATED AMOUNT OF 2729 CFMS. PLEASE SEE SECTION 304.9.3
 FBC FG: WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  