| 2022-03-17 13:12:44 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21110639 |
| | 3/17/22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS # FROM THE 1ST |
| | REVIEW REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) SHEETS P2 & P4: PROVIDE COMBUSTIONS AIR CALCULATIONS |
| | FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR |
| | WILL BE PROVIDED- SEC. 304.1 FBC FG. THE ENGINEER?S |
| | RESPONSE LETTER REFERS TO M1 FOR THE CALCULATIONS. M1 |
| | INDICATES 266 CFMS OF MECHANICALLY SUPPLIED COMBUSTION |
| | AIR TO IS TO BE PROVIDED BY THE MAKEUP AIR FAN FOR THE |
| | KITCHEN EXHAUST HOODS. REFER TO SHEET M-7 WHICH SHOWS |
| | 2320 CFMS OF MAKE UP AIR IS DEDICATED AS REPLACEMENT |
| | AIR FOR THE HOOD EXHAUST SYSTEM 1 WHICH IS SIZED AT A |
| | GREATED AMOUNT OF 2729 CFMS. PLEASE SEE SECTION 304.9.3 |
| | FBC FG: WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |