Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-03-16 14:49:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 MR AJ WASSON:
  
 THANK YOU FOR YOUR LETTER ADDRESSING MY EMAIL COMMENTS
 AND THE INFORMATION PROVIDED ON THE NATURE OF YOUR
 BUSINESS.
  
 UNDER THE DEFINITION OF USE IN YOUR LETTER YOU USED
 WORDS; DRINKING PLACE, FULL SERVICE RESTAURANT, BAR AND
 THE TERM I PROVIDED, NIGHTCLUB.
  
 THE BUSINESS TAX INFORMATION MAY NOT SPECIFICALLY
 INDICATE EXACTLY WHAT A BUSINESS OCCUPANCY FALLS UNDER
 PER THE LIFE SAFETY NOR BUILDING CODE.
  
 THAT IS WHY IT IS SO IMPORTANT TO CONDUCT INSPECTIONS
 AND REVIEW THE NATURE AND PURPOSE OF THE BUSINESS WHAT
 THEY DO AND WHAT THEY PROVIDE.
  
 NFPA DOES PROVIDE CODE FOR TERMS NOT EXPRESSLY DEFINED
 IN NFPA 101 CH 3, DEFINITIONS.
  
 3.1 GENERAL
 THE DEFINITIONS CONTAINED IN THIS CHAPTER SHALL APPLY
 TO THE TERMS USED
 IN THIS CODE. WHERE TERMS ARE NOT DEFINED IN THIS
 CHAPTER OR WITHIN
 ANOTHER CHAPTER, THEY SHALL BE DEFINED USING THEIR
 ORDINARILY ACCEPTED
 MEANINGS WITHIN THE CONTEXT IN WHICH THEY ARE USED.
 MERRIAM-WEBSTER?S
 COLLEGIATE DICTIONARY, 11TH EDITION, SHALL BE THE
 SOURCE FOR THE ORDINARILY
 ACCEPTED MEANING.
  
 PER MERRIAM-WEBSTER?S
 COLLEGIATE DICTIONARY, 11TH EDITION
  
 DEFINITION OF NIGHTCLUB
  
 : A PLACE OF ENTERTAINMENT OPEN AT NIGHT USUALLY
 SERVING FOOD AND LIQUOR AND PROVIDING MUSIC AND SPACE
 FOR DANCING AND OFTEN HAVING A FLOOR SHOW
  
 THE TERM DRINKING PLACE, FULL SERVICE RESTAURANT AND
 BAR ARE ALSO NOT DEFINED IN NFPA 101.
  
 MERRIAM-WEBSTER DOES NOT PROVIDE A DEFINITION FOR
 DRINKING PLACE NOR FULL SERVICE RESTAURANT. IT DOES FOR
 BAR.
  
 A COUNTER AT WHICH FOOD OR ESPECIALLY ALCOHOLIC
 BEVERAGES ARE SERVED
 WE SAT AT THE BAR WHILE WE WAITED FOR A TABLE.
 B: A ROOM OR ESTABLISHMENT WHERE ALCOHOLIC DRINKS AND
 SOMETIMES FOOD ARE SERVED : BARROOM
 THEY WENT TO A BAR FOR DRINKS.
  
 I HAVE NO OBJECTION TO INCLUDE BAR AS A PART OF YOUR
 OCCUPANCY; HOWEVER, IF STILL FALLS UNDER THE
 REQUIRMENTS OF NFPA 101, CH12 NEW ASSEMBLY OCCUPANCY.
  
 THE TERM NIGHTCLUB IS USED IN THE CODE TO HELP DEFINE
 WHAT ELSE OCCURS WITHIN AN THAT OCCUPANCY THAT SEPARATE
 IT FROM A BAR, FULL SERVICE RESTAURANT OR DRINKING
 PLACE.
  
 UNDER YOUR OWNER POSITION 1, 2 & 3 YOU DESCRIBE AN OPEN
 FLEX SPACE WHERE YOU WOULD REMOVE THE POOL TABLES FOR
 LIVE ENTERTAINMENT FOR COMIC'S, DRAG SHOWS, GUITARIST
 OR ANY OTHER LIVE ENTERTAINMENT.
  
  
 AS I PROVIDED IN MY EMAIL:
  
 THE REQUIREMENTS OF 12.3.5.1 FOR NEW NIGHTCLUB-TYPE
 ASSEMBLY
 OCCUPANCIES TO BE SPRINKLERED, AND OF 13.3.5.1 FOR
 EXISTING NIGHTCLUB TYPE
 ASSEMBLY OCCUPANCIES WITH MORE THAN A 100-PERSON
 OCCUPANT
 LOAD TO BE SPRINKLERED, WERE ADDED TO THE CODE IN 2006.
 THE PROVISIONS
 WERE DEVELOPED IN RESPONSE TO THE FEBRUARY 2003 FIRE AT
 THE
 STATION NIGHTCLUB IN WEST WARWICK, RHODE ISLAND, WHICH
 CLAIMED
 100 LIVES. THE FIRE AND THE KEY FINDINGS RELATED TO
 EMERGENCY EGRESS
 REPORTED BY THE NATIONAL INSTITUTE OF STANDARDS AND
 TECHNOLOGY
 (NIST) ARE DESCRIBED IN THE COMMENTARY FOLLOWING
 12.2.3.8.
  
 WHAT FIRE SPRINKLERS PROTECTION PROVIDES IS FOR THE
 CONTROL OF FIRE AND TIME FOR PATRONS TO EXIT.
  
 IT ALSO DOES NOT LIMIT, TO SOME EXTENT, WHAT THE
 OCCUPANCY CAN PROVIDE OR DO.
  
 YOU ARE ALLOWED TO HAVE A BAND, FLOOR SHOWS, DANCES AND
 OTHER LIVE ENTERTAINMENT EVENTS. AND YOU CAN PROVIDE
 THESE EVENTS ON A REGULAR BASIS BECAUSE THAT IS WHAT
 YOUR OCCUPANCY IS DESIGNED FOR.
  
 YOU HAVE PROVIDED A FEW NAMES OF BUSINESSES THAT MAY OR
 MAY NOT CONDUCT SIMILAR ACTIVITIES AND MANY OF WHICH
 HAVE FIRE SPRINKLER SYSTEMS AND SOME MAY NOT. MANY OF
 THOSE ARE NIGHTCLUBS SOME MAY NOT.
  
 HOWEVER, IF THEY ARE PRODUCING EVENTS OUTSIDE OF THE
 OCCUPANCY CLASSIFICATION IT IS NOT WITH PERMISSION NOR
 APPROVAL OF THIS OFFICE.
  
 BASED ON REVIEW OF THE DEFINITION OF NIGHTCLUB ABOVE
 AND THE INFORMATION YOU PROVIDED YOUR PROPOSED
 OCCUPANCY CONTINUES TO MEET THE NIGHTCLUB THRESHOLD.
  
 THE PLAN REVIEW COMMENT FOR THE INSTALLATION OF FIRE
 SPRINKLER PROTECTION REMAINS WITH ALL OTHER FIRE REVIEW
 COMMENTS BEING ADDRESSED.
  
 HOWEVER, SHOULD YOU STILL WANT TO PROCEED WITH
 OBJECTION TO THIS REQUIREMENT, I WILL REVIEW A DETAILED
 LETTER SIGNED AND SEALED FROM A FIRE PROTECTION
 ENGINEER AND OR A WRITTEN NFPA (NATIONAL FIRE
 PROTECTION ASSOCIATION) EXPERT OPINION THAT CONTAINS
 SPECIFIC FIRE CODE REFERENCES AND NARRATIVE POINTS THAT
 OUTLINE WHY YOUR OCCUPANCY DOES OR DOES NOT MEET THE
 NIGHTCLUB THRESHOLD FOR CONSIDERATION.
  
 RESPECTFULLY SUBMITTED,
  
 PETER LEDUC
 FIRE MARSHAL
  
  
  