Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-11 11:32:171ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110639
 1/11/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A.101, LS100 & P SHEETS: PROVIDE PLUMBING
 FIXTURE CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE CURRENT PLAN INDICATES
 A DEFICIENCY OF TWO WATER CLOSETS EACH FOR MALE AND
 FEMALE USE- (OCC. LOAD 168/2= 84 MALE AND FEMALE, 1 WC
 PER 40). AND TWO LAVATORIES EACH FOR MALE AND FEMALE
 USE- (1 PER 75). PLEASE NOTE THAT SEPARATE FACILITIES
 ARE REQUIRED FOR EACH SEX AND THE FIXTURES IN THE
 UNISEX RESTROOM CANNOT CONTRIBUTE TO THE NUBER OF
 FIXTURES REQUIRED FOR MALE AND FEMALE USE BECAUSE IT IS
 NOT A SINGLE USER UNISEX RESTROOM- SECS. 403.1.2,
 403.2, & 403.2.1 FBC P.
  
 2) SHEETS A.101 & A.800: THE TOILET ROOM DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACES REQUIRED FOR THE
 LAVATORIES UNLESS MEETING EXCEPTION 2 UNDER SEC.
 603.2.3 FBC ACC.
  
 3) A.800: MISSING ACCESSIBILITY COMPLIANCE DETAILS PER
 FBC ACC:
 A) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 FOR THE ACCESSIBLE URINAL AND LAVATORY IN THE UNISEX
 TOILET ROOM- SECS. 305, 605.3 & 606.2.
 B) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3
 C) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SEC. 604.6.
 D) SHOW THE CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND
 FIGURE 604.7.
 4) A.101 UNISEX TOILET ROOM: REFER TO SECS. 405.3.1 &
 405.3.5 FBC P AND PROVIDE-
 A) THE WIDTH OF THE TOILET COMPARTMENT.
 B) THE CENTERLINE OF THE LAVATORY MEASURED FROM THE
 SIDE WALL.
 C) THE CLEAR WIDTH MEASUREMENTS BETWEEN THE URINAL AND
 SINK PARTITIONS
 D) THE CLEAR WIDTH OPENING OF THE COMPARTMENT DOOR.
  
 5) P-1 & P-4: THE CLEAR WATER WASTE DRAINAGE FROM THE
 BAR AREAS INCLUDING HAND SINKS, FLOOR DRAINS AND FLOOR
 SINKS BELOW ICE BINS, COOLERS, ETC. SHALL NOT DRAIN
 INTO THE GREASE WASTE LINE AND INTERCEPTOR- SEC.
 1003.3.1 FBC P. PLEASE CORRECT THE PLANS.
  
 6) P-1, P-4, & P-5: THE CONDENSATE AND ICE MACHINE
 DRAINAGE CONVEYED BY THE FFD'S IN THE KITCHEN SHALL NOT
 DRAIN INTO THE GREASE WASTE INTERCEPTOR- SEC. 1003.3.1
 FBC P. PLEASE ROUTE THE DRAIN LINES TO THE SANITARY.
  
 7) P-1 & P-4: THERE APPEARS TO BE A MSSING FLOOR SINK
 AND DRAIN LINE FOR THE GLASS WASHER IN BAR 100-
 SEC.107.2.1 WPB.
  
 8) P-1, P-4, & P-5: PLACE A NOTE TO INDICATE THE GREASE
 INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE PERMIT-
 SECS. 105.1 & 107.2.1 WPB. PLEASE NOTE A SEPARATE PLAN
 SUBMITTAL IS REQUIRED. THE SUBMITTAL SHALL INCLUDE
 DRAWINGS, CALCULATIONS, AND MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS IN
 ACCORDANCE WITH SEC. 1003.3.5 FBC P.
  
 9) A103, P1, P2, P4: SHOW THE DWV AND WATER SUPPLY
 PIPING FOR THE WASHING MACHINE IN THE KITCHEN- SEC.
 406.2 FBC P.
  
 10) P-1, P-4, & P-5: REFERENCES ARE MADE TO CIVIL PLANS
 FOR CONNECTION POINTS OF POTABLE WATER, SANITARY AND
 STORM DRAINAGE PIPING TO MAINS AND LATERALS. PLEASE
 PROVIDE THE PLANS- SEC. 107.2.1 WPB.
  
 11) A103, P2 & P4: THE WATER PIPING PLAN AND ISO ARE
 MISSING THE SUPPLY PIPING TO THE GLASS WASHERS IN BAR
 100- SEC. 604.3, 604.9, & 608.3 FBC P.
  
 12) A103, P2 & P4: SHOW THE WATER SUPPLY PIPING TO THE
 FILTER SYSTEM AND LOCATION OF BACKFLOW PREVENTER
 DEVICE- SEC. 608.3 FBC P.
  
 13) P2 & P4: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P.
  
 14) P1 & P6: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK SHOWING EACH WELL OF THE FIXTURE
 DISCHARGING SEPARATELY INTO THE FLOOR SINK- SECTION
 802.1.1 FBC P.
  
 15) A300 & P3: THE ROOF DRAIN PLANS DO NOT MATCH-
 A) AREA DESIGNATIONS- 1, 2, & 3, AND SQUARE FOOTAGE
 CALCULATIONS.
 B) RAINFALL RATE.
 C) P3 PLAN DOES NOT PROVIDE CALCULATIONS FOR AREA 3 AS
 SHOWN ON A300.
 D) NO AREA CALCULATIONS, GPM FLOW, AND GUTTER SIZING
 PROVIDED FOR THE CANOPY ROOF, AND THE GUTTER IS NOT
 SHOWN ON P3.
 E) DOWNSPOUT DISCHARGES TO APPROVED DISPOSAL LOCATIONS
 NOT PROVIDED- SEE SEC. 1503.7 FBC B. IF CONNECTING TO
 UNDERGROUND STORM DRAIN PIPING PLEASE PROVIDE A
 DOWNSPOUT/STORM CONNECTION DETAIL AND SHOW THE PIPE
 ROUTING ON THE CIVIL PLANS.
  
 17) A301: PROVIDE A SCUPPER/DOWNSPOUT DETAIL, AND AN
 OVERFLOW SCUPPER DETAIL- SECS. 1503.4.2 & 1503.4.2.1
 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  