| 2022-01-11 11:32:17 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110639 |
| | 1/11/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A.101, LS100 & P SHEETS: PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC |
| | P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES. THE CURRENT PLAN INDICATES |
| | A DEFICIENCY OF TWO WATER CLOSETS EACH FOR MALE AND |
| | FEMALE USE- (OCC. LOAD 168/2= 84 MALE AND FEMALE, 1 WC |
| | PER 40). AND TWO LAVATORIES EACH FOR MALE AND FEMALE |
| | USE- (1 PER 75). PLEASE NOTE THAT SEPARATE FACILITIES |
| | ARE REQUIRED FOR EACH SEX AND THE FIXTURES IN THE |
| | UNISEX RESTROOM CANNOT CONTRIBUTE TO THE NUBER OF |
| | FIXTURES REQUIRED FOR MALE AND FEMALE USE BECAUSE IT IS |
| | NOT A SINGLE USER UNISEX RESTROOM- SECS. 403.1.2, |
| | 403.2, & 403.2.1 FBC P. |
| | |
| | 2) SHEETS A.101 & A.800: THE TOILET ROOM DOORS SHALL |
| | NOT SWING INTO THE CLEAR FLOOR SPACES REQUIRED FOR THE |
| | LAVATORIES UNLESS MEETING EXCEPTION 2 UNDER SEC. |
| | 603.2.3 FBC ACC. |
| | |
| | 3) A.800: MISSING ACCESSIBILITY COMPLIANCE DETAILS PER |
| | FBC ACC: |
| | A) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| | FOR THE ACCESSIBLE URINAL AND LAVATORY IN THE UNISEX |
| | TOILET ROOM- SECS. 305, 605.3 & 606.2. |
| | B) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED |
| | FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3 |
| | C) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH |
| | CONTROLS- SEC. 604.6. |
| | D) SHOW THE CENTERLINES OF THE TOILET PAPER DISPENSERS |
| | MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND |
| | FIGURE 604.7. |
| | 4) A.101 UNISEX TOILET ROOM: REFER TO SECS. 405.3.1 & |
| | 405.3.5 FBC P AND PROVIDE- |
| | A) THE WIDTH OF THE TOILET COMPARTMENT. |
| | B) THE CENTERLINE OF THE LAVATORY MEASURED FROM THE |
| | SIDE WALL. |
| | C) THE CLEAR WIDTH MEASUREMENTS BETWEEN THE URINAL AND |
| | SINK PARTITIONS |
| | D) THE CLEAR WIDTH OPENING OF THE COMPARTMENT DOOR. |
| | |
| | 5) P-1 & P-4: THE CLEAR WATER WASTE DRAINAGE FROM THE |
| | BAR AREAS INCLUDING HAND SINKS, FLOOR DRAINS AND FLOOR |
| | SINKS BELOW ICE BINS, COOLERS, ETC. SHALL NOT DRAIN |
| | INTO THE GREASE WASTE LINE AND INTERCEPTOR- SEC. |
| | 1003.3.1 FBC P. PLEASE CORRECT THE PLANS. |
| | |
| | 6) P-1, P-4, & P-5: THE CONDENSATE AND ICE MACHINE |
| | DRAINAGE CONVEYED BY THE FFD'S IN THE KITCHEN SHALL NOT |
| | DRAIN INTO THE GREASE WASTE INTERCEPTOR- SEC. 1003.3.1 |
| | FBC P. PLEASE ROUTE THE DRAIN LINES TO THE SANITARY. |
| | |
| | 7) P-1 & P-4: THERE APPEARS TO BE A MSSING FLOOR SINK |
| | AND DRAIN LINE FOR THE GLASS WASHER IN BAR 100- |
| | SEC.107.2.1 WPB. |
| | |
| | 8) P-1, P-4, & P-5: PLACE A NOTE TO INDICATE THE GREASE |
| | INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE PERMIT- |
| | SECS. 105.1 & 107.2.1 WPB. PLEASE NOTE A SEPARATE PLAN |
| | SUBMITTAL IS REQUIRED. THE SUBMITTAL SHALL INCLUDE |
| | DRAWINGS, CALCULATIONS, AND MANUFACTURER?S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS IN |
| | ACCORDANCE WITH SEC. 1003.3.5 FBC P. |
| | |
| | 9) A103, P1, P2, P4: SHOW THE DWV AND WATER SUPPLY |
| | PIPING FOR THE WASHING MACHINE IN THE KITCHEN- SEC. |
| | 406.2 FBC P. |
| | |
| | 10) P-1, P-4, & P-5: REFERENCES ARE MADE TO CIVIL PLANS |
| | FOR CONNECTION POINTS OF POTABLE WATER, SANITARY AND |
| | STORM DRAINAGE PIPING TO MAINS AND LATERALS. PLEASE |
| | PROVIDE THE PLANS- SEC. 107.2.1 WPB. |
| | |
| | 11) A103, P2 & P4: THE WATER PIPING PLAN AND ISO ARE |
| | MISSING THE SUPPLY PIPING TO THE GLASS WASHERS IN BAR |
| | 100- SEC. 604.3, 604.9, & 608.3 FBC P. |
| | |
| | 12) A103, P2 & P4: SHOW THE WATER SUPPLY PIPING TO THE |
| | FILTER SYSTEM AND LOCATION OF BACKFLOW PREVENTER |
| | DEVICE- SEC. 608.3 FBC P. |
| | |
| | 13) P2 & P4: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. |
| | |
| | 14) P1 & P6: PROVIDE AN INDIRECT WASTE DETAIL FOR THE |
| | 3-COMPARTMENT SINK SHOWING EACH WELL OF THE FIXTURE |
| | DISCHARGING SEPARATELY INTO THE FLOOR SINK- SECTION |
| | 802.1.1 FBC P. |
| | |
| | 15) A300 & P3: THE ROOF DRAIN PLANS DO NOT MATCH- |
| | A) AREA DESIGNATIONS- 1, 2, & 3, AND SQUARE FOOTAGE |
| | CALCULATIONS. |
| | B) RAINFALL RATE. |
| | C) P3 PLAN DOES NOT PROVIDE CALCULATIONS FOR AREA 3 AS |
| | SHOWN ON A300. |
| | D) NO AREA CALCULATIONS, GPM FLOW, AND GUTTER SIZING |
| | PROVIDED FOR THE CANOPY ROOF, AND THE GUTTER IS NOT |
| | SHOWN ON P3. |
| | E) DOWNSPOUT DISCHARGES TO APPROVED DISPOSAL LOCATIONS |
| | NOT PROVIDED- SEE SEC. 1503.7 FBC B. IF CONNECTING TO |
| | UNDERGROUND STORM DRAIN PIPING PLEASE PROVIDE A |
| | DOWNSPOUT/STORM CONNECTION DETAIL AND SHOW THE PIPE |
| | ROUTING ON THE CIVIL PLANS. |
| | |
| | 17) A301: PROVIDE A SCUPPER/DOWNSPOUT DETAIL, AND AN |
| | OVERFLOW SCUPPER DETAIL- SECS. 1503.4.2 & 1503.4.2.1 |
| | FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |