Plan Review Notes
Plan Review Notes For Permit 21110639
Permit Number 21110639
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-12-27 10:08:12EGRESS DOORS SERVING 100 OR MORE PERSONS SHALL BE
 EQUIPPED WITH PANIC HARDWARE. FLORIDA FIRE PREVENTION
 CODE 7TH EDITION, LIFE SAFETY CODE, 12.2.2.2.3
 WHERE THE OCCUPANT LOAD EXCEEDS 100, THE ASSEMBLY
 OCCUPANCY SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM. FLORIDA
 FIRE PREVENTION CODE 7TH EDITION, LIFE SAFETY CODE
 12.3.5.1
 ON ANY STORY WITH REHABILITATION WORK AREAS INVOLVING
 OVER 50 PERCENT OF THE AREA OF THE STORY, A SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE STORY IN
 ACCORDANCE WITH THE REQUIREMENTS OF OTHER SECTIONS OF
 THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE
 OCCUPANCY. FLORIDA FIRE PREVENTION CODE 7TH EDITION,
 LIFE SAFETY CODE 43.6.4.2
 SHEET A101 FLOOR PLAN KEY NOTES #17 INDICATES A GATE
 WITH ALARM. PROVIDE MORE DETAIL ON THE LOCKING
 ARRANGEMENT FOR THIS GATE FOR COMPLIANCE WITH FLORIDA
 FIRE PREVENTION CODE 7TH EDITION, LIFE SAFETY CODE,
 12.2.2
  