| 2022-02-09 16:11:36 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110622 |
| | 2/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.3 DETAILS D & 10: PLEASE RELOCATE THE |
| | SHOWER CONTROLS TO THE OPPOSITE WALL SIDE WALL IN |
| | COMPLIANCE WITH SEC. 608.2.2.1 FBC ACC. THE RELOCATION |
| | WILL ALSO REQUIRE REVISION OF THE PLUMBING PLANS- SEC. |
| | 107.2.1 WPB. |
| | |
| | 2) A1.1, A1.2, A3.2, P1.1 & P2.1: THE PLUMBING PLANS |
| | SHOW THE TABLES WILL BE OBSTRUCTING THE CLEAR FLOOR |
| | SPACES FOR THE SINKS IN THE TREATMENT ROOMS. PLEASE |
| | INDICATE WHICH SINKS ARE INTENDED TO BE ACCESSIBLE PER |
| | SEC. 212.3 FBC ACC AND SHOW THE CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS AT THE SINKS- 606.2. |
| | |
| | 3) P2.1: THE WASHING MACHINE VALVES ARE NOT IN A |
| | LOCATION WHERE THEY CAN BE ACCESSED BECAUSE THEY ARE |
| | BEHIND THE STACKABLE W/D UNIT- SEC. 606.3 FBC P. |
| | |
| | 4) P2.1, P2.2, P3.1 & P3.2: PLEASE NOTE THAT ONLY |
| | LAVATORIES IN PUBLIC TOILET FACILITIES ARE REQUIRED TO |
| | HAVE COLD OR TEMPERED WATER- SEC. 419.5 FBC P. THE PLAN |
| | SHOWS A MASTER THERMOSTATIC VALVE DELIVERING HW AT 110 |
| | DEGREES F FOR ALL FIXTURES. PLEASE INDICATE HOW |
| | TEMPERED WATER WILL BE DELIVERED FROM THE LAVATORY |
| | FAUCET IN RESTROOM 136- SECS. 202 & 416.5 FBC P. A) |
| | PLEASE CORRECT THE LAVATORY LABELS FOR THE SINKS IN THE |
| | TREATMENT ROOMS. PLEASE LABEL THESE AS SINKS- SEC. |
| | 422.1 FBC P. |
| | |
| | 5) MANUFACTURER'S SPECIFICATIONS FOR THE FLOAT TANK |
| | HAVE BEEN SUBMITTED SHOWING A FILTRATION SYSTEM FOR THE |
| | UNIT. PLEASE SHOW THE LOCATION OF THE FILTRATION SYSTEM |
| | ON THE PLUMBING PLANS AND PROVIDE PLUMBING PIPING |
| | DETAILS INCLUDING THE POTABLE WATER CONNECTION, SHUT |
| | OFF VALVE AND BACKFLOW PREVENTER- SEC. 608.3 FBC P. A) |
| | REFER TO SEC. 608.4 FBC P AND PROVIDE WASTEWATER |
| | DISPOSAL DETAILS FOR THE SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |