Plan Review Notes
Plan Review Notes For Permit 21110622
Permit Number 21110622
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-09 16:11:362ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110622
 2/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.3 DETAILS D & 10: PLEASE RELOCATE THE
 SHOWER CONTROLS TO THE OPPOSITE WALL SIDE WALL IN
 COMPLIANCE WITH SEC. 608.2.2.1 FBC ACC. THE RELOCATION
 WILL ALSO REQUIRE REVISION OF THE PLUMBING PLANS- SEC.
 107.2.1 WPB.
  
 2) A1.1, A1.2, A3.2, P1.1 & P2.1: THE PLUMBING PLANS
 SHOW THE TABLES WILL BE OBSTRUCTING THE CLEAR FLOOR
 SPACES FOR THE SINKS IN THE TREATMENT ROOMS. PLEASE
 INDICATE WHICH SINKS ARE INTENDED TO BE ACCESSIBLE PER
 SEC. 212.3 FBC ACC AND SHOW THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS AT THE SINKS- 606.2.
  
 3) P2.1: THE WASHING MACHINE VALVES ARE NOT IN A
 LOCATION WHERE THEY CAN BE ACCESSED BECAUSE THEY ARE
 BEHIND THE STACKABLE W/D UNIT- SEC. 606.3 FBC P.
  
 4) P2.1, P2.2, P3.1 & P3.2: PLEASE NOTE THAT ONLY
 LAVATORIES IN PUBLIC TOILET FACILITIES ARE REQUIRED TO
 HAVE COLD OR TEMPERED WATER- SEC. 419.5 FBC P. THE PLAN
 SHOWS A MASTER THERMOSTATIC VALVE DELIVERING HW AT 110
 DEGREES F FOR ALL FIXTURES. PLEASE INDICATE HOW
 TEMPERED WATER WILL BE DELIVERED FROM THE LAVATORY
 FAUCET IN RESTROOM 136- SECS. 202 & 416.5 FBC P. A)
 PLEASE CORRECT THE LAVATORY LABELS FOR THE SINKS IN THE
 TREATMENT ROOMS. PLEASE LABEL THESE AS SINKS- SEC.
 422.1 FBC P.
  
 5) MANUFACTURER'S SPECIFICATIONS FOR THE FLOAT TANK
 HAVE BEEN SUBMITTED SHOWING A FILTRATION SYSTEM FOR THE
 UNIT. PLEASE SHOW THE LOCATION OF THE FILTRATION SYSTEM
 ON THE PLUMBING PLANS AND PROVIDE PLUMBING PIPING
 DETAILS INCLUDING THE POTABLE WATER CONNECTION, SHUT
 OFF VALVE AND BACKFLOW PREVENTER- SEC. 608.3 FBC P. A)
 REFER TO SEC. 608.4 FBC P AND PROVIDE WASTEWATER
 DISPOSAL DETAILS FOR THE SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
  
 MECHANICAL/PLUMBING PLANS EXAMINER