2022-02-02 06:50:58WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21110622
 ADD: 2511 S. DIXIE HWY.
 CONT: KOLOSVARY MANAGEMENT
 TEL: 412-400-8400
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 01ST/2022
 ACTION: DENIED
  
 1A) 2ND REQUEST. IF THE SPECIAL INSPECTION FORMS ARE TO
 BE USED, NOTE A THRESHOLD INSPECTOR IS THERE FOR THE
 LIFE OF THE JOB. THE OTHER ISSUE IS FOR THRESHOLD
 INSPECTIONS FORMS A WRITTEN THRESHOLD INSPECTION PLAN
 IS ALSO REQUIRED. I TRULY BELIEVE THAT IF YOU DO NOT
 WANT TO USE THE CITY INSPECTORS FOR THE BUILDING
 INSPECTION PORTION OF THE PROJECT RESIDENT INSPECTOR
 FORMS SHOULD BE SUBMITTED.
 1ST ROUND OF COMMENTS. SUBMITTED INSPECTION FORM IS FOR
 SPECIAL INSPECTOR (THRESHOLD BUILDINGS/ HIGHRISE) THE
 FORMS THAT SHOULD HAVE BEEN SENT ARE RESIDENT INSPECTOR
 FORMS. PLEASE ALSO GET IN CONTACT WITH THE ACTING CHIEF
 BUILDING INSPECTOR TO SEE WHAT INSPECTIONS THE CITY
 WILL DO, FOUNDATIONS, WINDOW BUCK INSPECTIONS, AND
 WHICH INSPECTIONS THE P.E. CARL FORBS WILL COMPLETE. IF
 THE SPECIAL INSPECTION FORMS ARE TO BE USED, THEN
 COMPLIANCE WITH:
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) SEMI-COMPLIED. THIS REVIEW MINIMUM BUILDING TYPE IS
 LABELED AS TYPE VA EXISTING, UNPROTECTED/ FULLY
 SPRINKLERED. DISCREPANCY TYPE VA IS 1 HOUR FIRE RATED
 SEE TABLE 601. BUILDING TYPE VB IS UNPROTECTED.
 1ST ROUND OF COMMENTS. CODE ANALYSIS DOES NOT PROVIDE
 THE MINIMUM BUILDING TYPE, NOR THE TOTAL SQUARE FOOTAGE
 OF THE BUILDING NOR THE REMAINDER OF THE BUILDING
 OCCUPANCY TYPE COMPLIANCE WITH TABLE 506.2 AND SECTION
 508.1 OF THE 2020 FBC-BUILDING CODE.
 .
 2) SHEET A1.2:
 2A-C) COMPLIED.
  
 2D) SEMI-COMPLIED. FLOAT ROOM SHEET A1.4 LIST PT-9 ON
 SHEET A1.5 FINISH MATERIALS THERE IS NO PT-9 THERE WAS
 A REVISION SHOWING A NEW FRP-1. IT WOULD APPEAR THE
 REVISION DID NOT CARRY OVER TO SHEET A1.4 IN THE FLOAT
 ROOM. DISCREPANCY IN PLANS, 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1ST ROUND COMMENTS. FLOAT ROOM 131 IT APPEARS TO HAVE A
 ACCESSIBLE SHOWER AND FLOAT TANK POD. I AM MISSING WHAT
 SHEET PROVIDES THE FINISH MATERIALS FOR BASE AND WALLS.
 SHEET A1.5 INDICATES THE FINISH MATERIAL TYPES.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
  
 3) COMPLIED.
  
 4) 2ND REQUEST. SHEET M1.2 NOTE # 2 INDICATES TO
 PROVIDE NEW MIAMI-DADE MIAMI TECH MECHANICAL UNIT ROOF
 TOP STAND NOA # 20-1013.03. THIS REVIEW NO PRODUCT
 APPROVAL WAS SUBMITTED. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (G) PRE-ENGINEERED A/ C STANDS.
  
 5) COMPLIED. MIAMI-DADE NOA 20-0401.14 CA-740F FIXED
 CASEMENT FIXED WINDOW-LMI.
  
 6) 2ND REQUEST. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC.
 THE MIAMI-DADE MIAMI TECH MECHANICAL UNIT ROOF TOP
 STAND NOA # 20-1013.03 NOR MIAMI-DADE NOA 20-0401.14
 CA-740F FIXED CASEMENT FIXED WINDOW-LMI SHOW COMPLIANCE
 WITH W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING (SHOP DRAWING STAMP OF APPROVAL) BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER