| Date |
Text |
| 2021-12-30 13:30:01 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110622 |
| | 12/30/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.3- DETAILS 5 & 8: SHOW THE TOILET SEAT |
| | MEASUREMENTS FROM THE FINISHED FLOORS TO THE TOPS OF |
| | THE SEATS- SEC. 604.4 FBC ACC. |
| | |
| | 2) A3.3- DETAILS 4 & 7: SHOW THE REAR WATER CLOSET GRAB |
| | BARS WILL BE 36-INCHES MINIMUM LENGTH AND SHALL EXTEND |
| | FROM THE CENTERLINE OF THE WATER CLOSETS 12 INCHES |
| | MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE OTHER |
| | SIDE- SEC. 604.5.2 FBC ACC. |
| | |
| | 3) A3.3 DETAILS D, 10, 11: SHOW THE SHOWER GRAB BARS |
| | WILL BE INSTALLED 6 INCHES MAXIMUM FROM THE ADJACENT |
| | WALLS- SEC. 608.3.2 FBC ACC. |
| | |
| | 4) A3.3 DETAIL 10: SHOW THE INSTALLATION HEIGHT OF THE |
| | SHOWER CONTROLS, FAUCETS, AND SHOWER SPRAY- SEC. |
| | 608.5.2 FBC ACC. |
| | |
| | 5) A3.3: PROVIDE SHOWER PAN DRAIN, LINER, AND WALL |
| | FINISH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 FBC P. |
| | |
| | 6) P1.1 & P1.2: THE WASHING MACHINE FIXTURE DRAIN SHALL |
| | CONNECT TO A 3-INCH STACK OR BRANCH DRAIN- SEC. 406.2 |
| | FBC P. |
| | |
| | 7) P2.1: SHOW THE LOCATIONS OF THE WASHING MACHINE |
| | SHUTOFF VALVES OR PROVIDE A NOTE TO INDICATE THEY WILL |
| | IN AN ACCESSIBLE LOCATION- SEC. 608.3 FBC P. |
| | |
| | 8) P2.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF |
| | SHUTOFF VALVES AND WATER HAMMER ARRESTORS- SECS. 606.1, |
| | 606.2 & 604.9 FBC P. |
| | |
| | 9) P2.1 & P2.2: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- SEC. 416.5 FBC P. |
| | |
| | 10) P3.1: PROVIDE THE MAKE AND MODEL OF SHOWER VALVE IN |
| | THE SCHEDULE AND SHOW COMPLIANCE WITH SEC. 412.3 FBC P. |
| | |
| | 11) P3.1: INCLUDE WATER CLOSET FLUSH VALVES IN THE |
| | FIXTURE CONNECTION SCHEDULE- TABLE 604.5 FBC P. |
| | |
| | 12) P3.2: PROVIDE AN ENLARGED WATER PIPING DETAIL FOR |
| | THE NEW WATER HEATERS SHOWING WATER PIPING SUPPLY AND |
| | RETURN CONNECTIONS, LOCATIONS OF CONTROLS, VALVES, |
| | EXPANSION TANK (IF REQUIRED), PRESSURE RELIEF PIPING, |
| | AND CONDENSATE PIPING- SECS. 502.1, 607.2.1- 607.3 FBC |
| | P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |