| 2021-12-20 13:39:20 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110622 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW WHERE THE OXYGEN WILL BE STORED AND THE | | | AMOUNTS FOR THE HYPERBARIC CHAMBER. FBC 107.2.1 | | | | | | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 3) PLEASE MAKE SURE THE BATH EXHAUST FANS WILL MEET THE | | | MINIMUM CFM REQUIREMENTS OF FBC M TABLE 403.3.1.1 FOOT | | | NOTE E 50 CFM IF CONTINUOUSLY OPERATED OR 70 CFM IF | | | INTERMITTENTLY OPERATED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|