Plan Review Notes
Plan Review Notes For Permit 21110622
Permit Number 21110622
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-05 09:17:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21110622
 ADD: 2511 S. DIXIE HWY.
 CONT: KOLOSVARY MANAGEMENT
 TEL: 412-400-8400
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 05/2022
 ACTION: DENIED
  
 1A) SUBMITTED INSPECTION FORM IS FOR SPECIAL INSPECTOR
 (THRESHOLD BUILDINGS/ HIGHRISE) THE FORMS THAT SHOULD
 HAVE BEEN SENT ARE RESIDENT INSPECTOR FORMS. PLEASE
 ALSO GET IN CONTACT WITH THE ACTING CHIEF BUILDING
 INSPECTOR TO SEE WHAT INSPECTIONS THE CITY WILL DO,
 FOUNDATIONS, WINDOW BUCK INSPECTIONS, AND WHICH
 INSPECTIONS THE P.E. CARL FORBS WILL COMPLETE. IF THE
 SPECIAL INSPECTION FORMS ARE TO BE USED, THEN
 COMPLIANCE WITH:
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 1B) CODE ANALYSIS DOES NOT PROVIDE THE MINIMUM BUILDING
 TYPE, NOR THE TOTAL SQUARE FOOTAGE OF THE BUILDING NOR
 THE REMAINDER OF THE BUILDING OCCUPANCY TYPE COMPLIANCE
 WITH TABLE 506.2 AND SECTION 508.1 OF THE 2020
 FBC-BUILDING CODE.
 2) SHEET A1.2:
 2A) THE RESTROOM 107 IS NOT DIMENSIONED CAN NOT TELL IF
 IT COMPLIES WITH THE REQUIRED MINIMUM DIMENSION FOR AN
 ACCESSIBLE RESTROOM.
 CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3. 604.3.1. SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR WALL.
 NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE 7-FOOT
 1 INCH (FINISHES MAY ENCROACH) ON THE FINISH
 DIMENSION!!!
  
 2B) ROOM 128 LABELED SALT SUITES ONLY HAS 3 WALLS, IS
 THERE A WALL MISSING? 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2C) ROOM 128 LABELED SALT SUITES, JUST TO THE RIGHT IS
 A SPACE MEASURED 8 FEET 1 INCH NO ROOM IDENTIFIER? 107.
 2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) FLOAT ROOM 131 IT APPEARS TO HAVE A ACCESSIBLE
 SHOWER AND FLOAT TANK POD. I AM MISSING WHAT SHEET
 PROVIDES THE FINISH MATERIALS FOR BASE AND WALLS. SHEET
 A1.5 INDICATES THE FINISH MATERIAL TYPES. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED. 2020 FBC-B
 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT
 OF THE BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN
 BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT
 IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT
 SURFACE.
  
 2D) 1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2D) 2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
  
  
 2D) 3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS
 AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY
 WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2D) 4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED
 AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND
 WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3) NONE OF THE ARCHITECTURAL, STRUCTURAL NOR MECHANICAL
 SHEETS INDICATE HOW ONE GAINS ACCESS TO THE ROOF TO
 SERVICE THE MECHANICAL EQUIPMENT. 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN
 HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN
 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT
 SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE USE OF
 PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER
 PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP
 OF THE PARAPET WALL.
  
 4) SHEET M1.2 NOTE # 2 INDICATES TO PROVIDE NEW
 MIAMI-DADE MIAMI TECH MECHANICAL UNIT ROOF TOP STAND
 NOA # 20-1013.03. THIS REVIEW NO PRODUCT APPROVAL WAS
 SUBMITTED. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (G)
 PRE-ENGINEERED A/ C STANDS.
  
 5) SUBMITTED A MIAMI-DADE NOA 20-0401.14 CA-740F FIXED
 CASEMENT FIXED WINDOW-LMI. SEMI-COMPLIED, PAGE 1 OF 11
 HIGHLIGHTED GLASS TYPE (2) BUT FAILED TO HIGHLIGHT ON
 PAGE 8 FOR WINDOW SIZE AND CORRESPONDING PRESSURES.
  
 6) THE MIAMI-DADE MIAMI TECH MECHANICAL UNIT ROOF TOP
 STAND NOA # 20-1013.03 NOR MIAMI-DADE NOA 20-0401.14
 CA-740F FIXED CASEMENT FIXED WINDOW-LMI SHOW COMPLIANCE
 WITH W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING (SHOP DRAWING STAMP OF APPROVAL) BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  