| Plan Review Notes For Permit 21110619 |
| Permit Number |
21110619 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-01-27 18:01:05 | RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21110619. | | | | | | 1- MISSING PRODUCT APPROVALS LISTED ON THE ENGINEER'S | | | REVISED WINDOW/DOOR SCHEDULE FOR: | | | A) OK. | | | | | | ORIGINAL COMMENT: | | | B)WINDOW #25: ALUMINUM WINDOW WALL SYSTEM NOA | | | 18-0319.09 AND 20-1118.02. | | | | | | RESPONSE: | | | NOA 20-1116.02 SUBMITTED DOESN'T MATCH NOA'S LISTED BY | | | THE ENGINEER ON THE WINDOW/DOOR SCHEDULE. PROVIDE | | | PRODUCT APPROVALS LISTED BY TH ENGINEER OF RECORD. | | | | | | REMAINDER: | | | WINDOW FALL PROTECTION (SECTION 702.4 FBC-EXISTING | | | BUILDING) | | | 1- WINDOW OPENING CONTROL DEVICE COMPLYING WITH ASTM | | | F2090 SHALL BE REQUIRED IF WINDOW SILL IS LESS THAN 24? | | | ABOVE FINISHED FLOOR. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|